Operating at 277V, this single-pole MCCB is compatible with Siemens P1 through P5 panelboards and switchboards. This panel-mount breaker serves as a replacement for legacy ED41B015 models when installed with the required mounting kit. Rated 35kA at 277V, the 3VA5195-5ED11-0AA0 utilizes a TM210 thermal-magnetic trip unit. It offers fixed thermal and magnetic settings, current-limiting capabilities, and a SWD rating for switching fluorescent lighting loads.
Which Siemens panelboards are compatible with the 3VA5195-5ED11-0AA0?
This 1-pole breaker is designed for use in Siemens P1, P2, P3, P4, and P5 panelboards, as well as compatible Siemens switchboards and motor control centers.
What is the frame size for the 3VA5195-5ED11-0AA0?
This breaker is built on the Siemens 3VA51 frame, which supports a maximum continuous current of 125A. This specific unit is factory-calibrated for a 15A continuous load.
Are wire lugs included with the 3VA5195-5ED11-0AA0?
No. The 0AA0 suffix in the catalog number indicates this breaker is shipped from the factory without lugs. Appropriate wire connectors or nut keepers must be ordered separately for field installation.
Is the 3VA5195-5ED11-0AA0 suitable for direct current (DC) systems?
Yes, this thermal-magnetic breaker is rated for DC applications up to 125VDC, providing a 50kA interrupting capacity.
Can the trip curve be adjusted on the 3VA5195-5ED11-0AA0?
No, this model features a TM210 thermal-magnetic trip unit with fixed long-time (thermal) and fixed instantaneous (magnetic) settings. The trip curve cannot be modified in the field.
Is this 3VA5 breaker suitable for reverse feed applications?
Yes, Siemens 3VA5 thermal-magnetic molded case circuit breakers are UL listed for reverse feed installations.
What specific fault protection does the LI trip function provide?
The LI designation indicates Long-Time and Instantaneous protection. The long-time thermal element protects the circuit against sustained overloads, while the instantaneous magnetic element trips the breaker immediately during a short circuit.
What does the breaking capacity class indicate for this breaker?
The digit 5 in the catalog number designates a Class M (Medium) breaking capacity. This provides an interrupting rating of 35kA at 277VAC and 85kA at 120VAC.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.8 out of 5 based on 8 reviews.