Built for commercial applications, the Siemens K3B150 is a 150A, three-pole molded case circuit breaker with an interchangeable trip unit. It provides essential long-time and instantaneous protection for industrial electrical systems. This legacy K-frame breaker mounts into older ITE and Siemens panelboards, offering an exact fit without modification. When upgrading panels, the FXD63B150 serves as its modern substitute but requires an adapter kit. Rated for up to 600VAC.
Which panelboards accept the K3B150 circuit breaker?
This bolt-on breaker is designed exclusively for legacy ITE and Siemens panelboards and switchboards configured for K-frame breakers. You must verify your panel interior labeling to confirm K-frame compatibility before installation.
Are ITE and Siemens K3B150 breakers interchangeable?
Yes. Siemens acquired the ITE electrical line and continued producing these K-frame breakers under the Siemens name. A Siemens K3B150 is an exact, interchangeable replacement for an original ITE K3B150.
What does the LI trip function code indicate on this breaker?
The LI designation means the trip unit provides Long-Time (L) and Instantaneous (I) protection. The Long-Time function handles sustained overloads using a fixed thermal element, while the Instantaneous function protects against short circuits using an adjustable magnetic element.
How is the magnetic trip adjusted on the K3B150?
The breaker features a fixed thermal element for long-time overload protection and an adjustable magnetic element for instantaneous short-circuit protection. The magnetic pickup can be adjusted using the dials on the front face of the trip unit to coordinate with your system fault current requirements.
Does the K3B150 require a specific mounting hardware kit?
Yes. As a bolt-on molded case circuit breaker, it requires the appropriate strap kit or mounting hardware specific to your ITE or Siemens panelboard or switchboard chassis. The required hardware is dictated by the panel type rather than the breaker itself.
Is it safe to install this Siemens K-frame breaker in a GE or Square D switchboard?
No. Circuit breakers must only be installed in panelboards and switchboards they are UL-listed for. Mixing brands without explicit cross-listing voids the UL certification and can lead to improper seating, overheating, and severe electrical hazards.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.