Delivering robust system protection, the Siemens 3VA5130-4ED31-0AA0 3-pole MCCB handles heavy-duty commercial power distribution. This unit integrates into Siemens 3VA panelboards, and fits P1 panels when equipped with a mounting kit. It is the designated replacement for the discontinued ED63B030 breaker. The device features a fixed TM210 thermal-magnetic trip unit for precise LI protection. It carries an S-Class breaking capacity of 65kA at 240V.
None (Standard 0AA0 suffix indicates no auxiliary switches or releases)
Standards
HACR, IEC 60947-2, UL 489
Approval
CE, CSA, EAC, UL, VDE
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Current Limiting, Class S Breaking Capacity, HID Rated
Product FAQs
9 answers
What frame size is the Siemens 3VA5130-4ED31-0AA0?
This circuit breaker belongs to the Siemens 3VA51 frame size, which supports a maximum continuous current rating of 125 amps.
Can the 3VA5130-4ED31-0AA0 be reverse fed?
Yes, Siemens 3VA5 thermal magnetic circuit breakers are UL listed for reverse feed applications. This allows line power to be connected to either the top or bottom terminals.
Is this circuit breaker suitable for direct current applications?
Yes, this thermal magnetic breaker is rated for DC systems. It provides an interrupting capacity of 50kA at 500VDC.
What is required to mount this breaker in a Siemens P1 panelboard?
Installing this 3VA51 frame breaker into a Siemens P1 panelboard requires a compatible breaker mounting kit. The specific kit depends on the panelboard generation and whether it is being used as a main or subfeed breaker.
What type of trip unit is installed in the 3VA5130-4ED31-0AA0?
This breaker features a TM210 thermal magnetic trip unit. It provides fixed long time (thermal) and fixed instantaneous (magnetic) protection settings.
Can this molded case circuit breaker be mounted on a DIN rail?
Yes, the 3VA51 frame can be DIN rail mounted using the appropriate Siemens DIN rail adapter accessory, making it suitable for industrial control panels.
What does the S interrupting class mean for this breaker?
The S class designates this as a Standard breaking capacity circuit breaker within the Siemens 3VA portfolio, providing a 25kA interrupting rating at 480VAC.
Are the thermal and magnetic trip settings adjustable on this model?
No, the TM210 trip unit on this specific breaker has fixed thermal and fixed magnetic trip settings. It does not offer field adjustability.
Does this breaker support internal accessories like shunt trips or auxiliary switches?
Yes, the Siemens 3VA51 frame features internal accessory pockets that can accept field-installable auxiliary switches, alarm switches, and shunt trips.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 4.8 out of 5 based on 8 reviews.