Skip to main content
Expedited shipping available at checkout

Siemens CND63B100 Molded Case Circuit Breaker

  • 1000A
  • 3 Pole
  • Unit Mount
Siemens CND63B100
Molded Case Circuit Breaker
Brand Siemens
SKU CND63B100
Select Item Condition
Earn 10440 SuperPoints
  • 1000A
  • 3 Pole
  • Unit Mount

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Siemens CND63B100 - 1000A 3 Pole Molded Case Circuit Breaker

New

$10,440.00 In Stock

Quantity

Description

Designed for high-capacity industrial systems, the CND63B100 is a 3-pole, 1000A molded case circuit breaker from the Siemens Sentron ND Frame series. It provides exceptional current-limiting capabilities with an interrupting rating of 100kA at 480VAC. This unit mounts into Siemens S4, S5, P4, and P5 panelboards, switchboards, and motor control centers. Equipped with a thermal-magnetic trip unit, it ensures precise long-time and instantaneous (LI) protection. Lugs are sold separately.

Specifications

Key specifications
Brand Siemens
Part Number CND63B100
Series CND6
Amperage 1000A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 480VAC, 600VAC, 500VDC
Phase 3
AIC Rating 200kA @ 240VAC, 100kA @ 480VAC, 65kA @ 600VAC, 50kA @ 500VDC
Fit and installation
Frame Type CND
Terminal Type Lugs
For Use With Siemens Sentron Panelboards (S4, S5, P4, P5), Switchboards (SB1, SB2, SB3), Motor Control Centers
Wire Gauge (4) 250-500 kcmil (Cu/Al)
Max Wire 500 kcmil
Min Wire 250 kcmil
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Lug Kits
Accessories Lugs Not Included
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval CSA, IEC, UL
Temp Rating 40C
Construction Features Current Limiting, HACR Rated, Non-Interchangeable Trip

Product FAQs

7 answers
Which Siemens panelboards and switchboards are compatible with the CND63B100?

This breaker is designed for use in Siemens Sentron S4, S5, P4, and P5 panelboards, as well as SB1, SB2, and SB3 switchboards and compatible motor control centers.

What are the wire size requirements for the terminal lugs on this breaker?

The standard lugs accept four 250 to 500 kcmil copper or aluminum conductors per phase.

How is the thermal magnetic trip unit configured on this model?

It features a fixed thermal element for long-time overload protection and an adjustable magnetic element for instantaneous short-circuit protection.

Is the CND63B100 suitable for direct current (DC) systems?

Yes, it is rated for use in DC applications up to 500VDC, providing a 50kA interrupting rating.

What type of protection does the LI trip function provide?

The LI designation means the breaker provides Long-Time (L) protection against sustained overloads and Instantaneous (I) protection against severe short circuits.

Does this breaker plug into the busbar or bolt on?

This is a unit mount, bolt-on circuit breaker. It requires bolted connections to the busbar or mounting assembly rather than a plug-in connection.

What frame size category does this breaker fall under?

It is part of the Siemens Sentron ND frame group, specifically utilizing the CND frame type.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.