Siemens CND63B120 3 Pole Circuit Breaker

Siemens CND63B120 - 1200A 3 Pole Molded Case Circuit Breaker

Re-Certified

$2,479.98 Check Stock

Quantity

Description

Engineered for heavy-duty commercial use, the CND63B120 is a 1200A thermal-magnetic MCCB from the Sentron ND Frame family. It provides fixed thermal and adjustable magnetic trip settings for LI fault protection. Designed for unit-mount installations, this breaker fits into Siemens S4, S5, P4, and P5 panelboards, plus SB-series switchboards. It requires separate lug kits for up to four 250-500 kcmil cables per phase. With a 100 kAIC rating at 480V, this fuseless breaker is HACR rated.

Specifications

Key specifications
Brand Siemens
Series CND6
Amperage 1200A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 480VAC, 600VAC, 500VDC
Phase 3
AIC Rating 200kA @ 240VAC, 100kA @ 480VAC, 65kA @ 600VAC, 50kA @ 500VDC
Fit and installation
Frame Type CND
Terminal Type Lugs
For Use With Siemens Sentron Panelboards (S4, S5, P4, P5), Switchboards (SB1, SB2, SB3), Motor Control Centers
Wire Gauge (4) 250-500 kcmil (Cu/Al)
Max Wire 500 kcmil
Min Wire 250 kcmil
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Lug Kits
Accessories Lugs Not Included
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval CSA, IEC, UL
Temp Rating 40C
Construction Features Current Limiting, HACR Rated, Non-Interchangeable Trip

Product FAQs

5 answers
Which Siemens panelboards and switchboards are compatible with the CND63B120?

This 1200A breaker is designed for installation in Siemens Sentron S4, S5, P4, and P5 panelboards, as well as SB1, SB2, and SB3 switchboards and motor control centers.

What wire sizes and materials do the standard lugs on this breaker accept?

The included lugs accept four 250 to 500 kcmil copper or aluminum conductors per phase.

How does the adjustable magnetic trip function work on the CND63B120?

This breaker features a fixed thermal element for standard overload protection and an adjustable magnetic element. The adjustable magnetic trip allows electricians to fine-tune the instantaneous short-circuit response to match specific load requirements and coordinate with other protective devices.

Can the CND63B120 replace older I-T-E or Siemens ND frame breakers?

Yes, this Sentron series CND frame breaker is physically interchangeable with legacy I-T-E and Siemens ND6 or CND6 frame breakers of the same amperage. It fits the same panel space and uses identical mounting dimensions.

What type of protection does the thermal magnetic trip unit provide?

The thermal magnetic mechanism provides dual protection: the thermal element responds to heat generated by prolonged overloads, while the magnetic element reacts almost instantly to high fault currents to clear short circuits safely.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.