Engineered for heavy-duty commercial and industrial applications, the Siemens HLMD63B700 is a 3-pole, 700-amp molded case circuit breaker. It belongs to the Sentron LMD frame family, providing reliable overcurrent and short-circuit protection for high-capacity electrical systems. This unit-mount breaker installs into Siemens Sentron panelboards, switchboards, and individual enclosures. Rated at 65 kAIC at 480VAC, it utilizes thermal-magnetic trip technology and supports reverse feed setups.
HACR Rated, High Interrupting Capacity, Interchangeable Trip Unit
Product FAQs
8 answers
What equipment is compatible with the HLMD63B700 circuit breaker?
This breaker mounts in Siemens Sentron panelboards, switchboards, and standalone enclosures designed to accept LMD frame breakers.
What wire sizes are supported by the standard lugs?
The factory-installed TA3K500 line and load lugs accept up to three 1/0 AWG to 500 kcmil copper or aluminum conductors per phase.
How is the trip unit adjusted on this breaker?
The thermal-magnetic trip unit features a fixed thermal element for long-time overcurrent protection and an adjustable magnetic element for instantaneous short-circuit protection.
Can this breaker be used in DC power systems?
Yes, the HLMD63B700 is rated for use in DC systems up to 500VDC, providing an interrupting capacity of 50kAIC.
Are the trip units on the HLMD63B700 interchangeable?
Yes, the Sentron LMD frame utilizes an interchangeable trip design. This allows the thermal-magnetic trip unit to be swapped without removing the breaker frame from the panel.
What are the physical dimensions of this LMD frame breaker?
The breaker measures 16 inches in height, 7.5 inches in width, and 4.5 inches in depth.
What safety standards apply to this Siemens breaker?
It is UL 489 listed for low-voltage power distribution and is HACR rated for heating, air conditioning, and refrigeration applications.
What is the difference between the LMD and HLMD frame breakers?
The HLMD frame offers a higher interrupting capacity than the standard LMD frame. The HLMD63B700 provides 65kAIC at 480VAC, while the standard LMD equivalent provides 50kAIC at 480VAC.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.