Built for overcurrent and GFCI protection, the Eaton QB3050GF miniature circuit breaker is rated 50A with 3 poles, 208Y/120VAC operation and a 10kAIC interrupting rating. This Quicklag QB series breaker uses bolt-on mounting and lug terminals for 14-4 AWG wire. Its fixed thermal magnetic trip provides long-time and instantaneous functions. It has a single circuit arrangement, 3-phase operation and UL approval.
How should I select the Eaton QB3050GF for circuit current?
Use its 50A rating when evaluating the circuit load and conductor ampacity. The trip settings are fixed, so choose the required current rating rather than relying on field adjustment.
How do I check whether the interrupting rating is adequate?
Compare the available fault current at the installation point with the breaker's 10kAIC interrupting rating. The available fault current must not exceed that rating.
Does this breaker provide both overcurrent and GFCI protection?
Yes. Overcurrent protection addresses overloads and short circuits, while GFCI protection detects current leakage to ground. Choose it when the circuit requires both protection functions.
How does the thermal-magnetic trip respond to overloads and short circuits?
The thermal-magnetic trip includes long-time and instantaneous functions. The thermal response allows delayed tripping for sustained overloads, while the magnetic response trips rapidly for high-current faults.
How is this breaker mechanically secured?
It uses bolt-on mounting, so installation involves securing the breaker with bolts. Account for that fastening method when planning installation access and tools.
What conductor sizes can be terminated at the breaker?
The lug terminals accept a wire range of 14-4 AWG. Select a conductor within that range whose ampacity meets the circuit requirements; terminal acceptance alone does not determine conductor ampacity.
What dimensions should I use for layout planning?
The breaker measures 3 in high, 4.25 in long and 3 in wide. Use these dimensions to plan its physical footprint and the surrounding installation workspace.
What voltage and phase ratings should I check when selecting this breaker?
The Eaton QB3050GF is rated 208Y/120VAC, three-phase, with three poles. Compare the circuit voltage, phase and required pole count with these ratings when selecting circuit protection.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.