ABB / General ElectricTEYD2060B
Quantity
New
Quantity
ABB / General ElectricTEYD2060B
ABB / General ElectricTEYH2060B
| Brand | ABB / General Electric |
|---|---|
| Series | TEYF |
| Amperage | 60A |
| Poles | 2 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 277VAC, 480Y/277VAC, 250VDC, 120/240VAC |
| Phase | 1 |
| AIC Rating | 65kA @ 240VAC, 18kA @ 277VAC, 18kA @ 480Y/277VAC, 10kA @ 250VDC, 65kA @ 120/240VAC |
| Frame Type | TEYF |
|---|---|
| Terminal Type | Lugs |
| For Use With | GE A-Series Lighting Panelboards |
| Wire Gauge | 10-4 AWG (Cu/Al) |
| Max Wire | 4 AWG |
| Min Wire | 10 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm |
|---|---|
| Accessories | Load Side Lugs Included |
| Standards | CSA C22.2 No. 5.1, UL 489 |
| Approval | CSA, HACR, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Common Trip, Quick-Make/Quick-Break, Non-Interchangeable Trip, Reverse Feed |
The TEYF260 is designed for use in GE A-Series lighting panelboards. It features a bolt-on mounting design that connects directly to the panelboard bus.
The primary difference is the interrupting capacity at 480Y/277VAC. The standard TEY260 is rated at 14kAIC, while the TEYF260 offers an upgraded 18kAIC rating. Both share the same physical dimensions and bolt-on mounting for A-Series panelboards.
Yes, the TEYF260 shares the same physical footprint as the TEYD, TEYH, and TEYL series. However, you must verify that your system's available fault current does not exceed the TEYF260's 18kAIC rating at 480Y/277VAC, as the D, H, and L variants have higher interrupting capacities of 25kAIC, 35kAIC, and 65kAIC respectively.
For the factory-installed lugs accepting 10-4 AWG copper or aluminum wire, the required torque is 35 in-lb for #10 AWG, 40 in-lb for #8 AWG, and 45 in-lb for #6 to #4 AWG conductors.
Yes, this breaker is rated for DC applications up to 250VDC with an interrupting capacity of 10kAIC. This makes it suitable for specific control circuits or battery systems that fall within these parameters.
Yes. While it is primarily designed to bolt onto GE A-Series panelboards, it can be used in standalone lug-to-lug applications by utilizing a separate TEY3B mounting base.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.