Skip to main content
Expedited shipping available at checkout

Square D LCP36600 Molded Case Circuit Breaker

  • 600A
  • 3 Pole
  • Bolt-On
Square D LCP36600
Molded Case Circuit Breaker
Brand Square D
SKU LCP36600
Select Item Condition
Earn 2950 SuperPoints
  • 600A
  • 3 Pole
  • Bolt-On

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Square D LCP36600 - 600A 3 Pole Molded Case Circuit Breaker

Re-Certified

$2,950.00 In Stock

Quantity

Description

Engineered for commercial power systems, the Square D LCP36600 is a 600A, 3-pole molded case circuit breaker. Designed for bolt-on mounting, this L-Frame breaker fits Square D switchboards and enclosures. It serves as a direct substitute for LCL36600 and LLL36600 breakers. Note that replacing this unit with the modern LJL36600 requires a specific retrofit kit. Delivering a 65kA interrupting rating at 480VAC, it includes load side lugs accepting (2) 2/0 AWG to 500 kcmil wire.

Specifications

Key specifications
Brand Square D
Series LCP
Amperage 600A
Poles 3
Mounting Style Bolt-On
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Phase 3
AIC Rating 100kA @ 240VAC, 65kA @ 480VAC, 35kA @ 600VAC, 10kA @ 250VDC
Fit and installation
Frame Type L
Terminal Type Lugs
For Use With Square D Switchboards, Motor Control Centers, Enclosures
Wire Gauge (2) 2/0 AWG-500 kcmil (Al/Cu)
Max Wire 500 kcmil
Min Wire 2/0 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch
Accessories Load Side Lugs Included
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval CSA, HACR, IEC, UL
Temp Rating 40C
Construction Features HACR Rated, Extra High Interrupting Capacity

Product FAQs

7 answers
Is the LCP36600 still manufactured, or is there a modern replacement?

The LCP36600 is a legacy L-Frame breaker. For modern replacements, Square D transitioned to the PowerPact L-frame series. Exact cross-referencing to a PowerPact model depends on your specific panel, mounting, and trip unit requirements.

Can I install the LCP36600 in a Square D I-Line panelboard?

No. The LCP36600 features a bolt-on connection designed for unit-mount applications in switchboards, motor control centers, and enclosures. For an I-Line panelboard, you must use the plug-on equivalent, such as the LC36600.

How is the trip unit adjusted on the LCP36600?

The thermal protection (Long-Time) is fixed at 600 amps. The magnetic protection (Instantaneous) features an adjustable dial on the face of the breaker, allowing electricians to fine-tune the short-circuit trip threshold to coordinate with other devices in the electrical system.

Can I wire this 600A breaker using a single conductor per phase?

No. Standard wire sizes like 500 kcmil max out around 380 amps at 75C. To safely carry the full 600A load, you must use parallel conductors. The standard lugs on the LCP36600 accommodate two conductors per phase, ranging from 2/0 AWG to 500 kcmil (Al/Cu).

Why is it important to use a calibrated torque wrench when installing this breaker?

Under-torquing can lead to high-resistance connections, overheating, and potential fire hazards, while over-torquing can damage the conductor strands or lug body. NEC 110.14(D) requires the use of a calibrated torque tool to ensure connections meet the manufacturer's exact specifications printed on the breaker label.

Can the LCP36600 be reverse fed?

Standard thermal-magnetic L-frame breakers without Line and Load markings are generally suitable for reverse feeding. However, always check the physical breaker faceplate. If it is explicitly marked Line and Load, it must be wired in that specific direction to comply with NEC 240.81.

How should the LCP36600 be wired for 250VDC applications?

When using this breaker in a 250VDC system, it typically requires wiring multiple poles in series to safely interrupt the DC arc. Always consult the Square D wiring diagrams and NEC guidelines for proper multi-pole DC configurations.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.