Part of the Allen-Bradley Bulletin 140U line, the 140U-I6C3-C15 is a 3-pole, 15A molded case circuit breaker built for commercial and industrial applications. It features fixed thermal and magnetic trip settings for reliable LI protection. This I-Frame unit mounts into industrial control panels and motor control centers. It is functionally replaced by the newer 140G-H6C3-C15 model for future upgrades. Rated at 65kAIC at 480VAC, it provides robust current-limiting performance and is HACR rated.
"140U" is the Allen Bradley molded case circuit breaker series. "I" indicates the I-Frame size. "6" specifies the 65kA at 480VAC interrupting rating. "C3" denotes a 3-pole configuration, and "C15" represents the 15A continuous current rating.
What does the "LI" trip function code mean for this breaker?
The "LI" code indicates that the thermal-magnetic trip unit provides Long-Time (L) overload protection and Instantaneous (I) short-circuit protection. Both the thermal and magnetic trip points are fixed on this model.
Where is the 140U-I6C3-C15 typically installed?
This unit-mount, bolt-on breaker is designed for use in industrial control panels and motor control centers requiring reliable branch circuit protection.
Is the 140U-I6C3-C15 part of an active or legacy product line?
The 140U series is a legacy product line. Rockwell Automation has introduced newer series, such as the 140G and 140UT, as modernization paths for these older molded case circuit breakers.
Does this breaker provide adjustable trip settings?
No, the 140U-I6C3-C15 features a fixed thermal and fixed magnetic trip unit. If your application requires adjustable overload or short-circuit settings, a different frame or trip unit type is required.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.