Delivering advanced microprocessor-based protection, the Square D PLA34120U44A is a 3-pole, 1200A molded case circuit breaker. This PowerPacT P-Frame unit is engineered for facilities requiring highly configurable trip settings. The breaker features an I-Line plug-on connection, allowing it to mount into Square D I-Line panelboards and switchboards. At its core is the Micrologic 6.0A trip unit, featuring a built-in ammeter and fully adjustable LSIG functions with 100kAIC at 480V.
Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Communication Module, Rating Plugs
Accessories
Micrologic 6.0A Trip Unit
Standards
CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, IEC, NOM, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Current Limiting, True RMS Sensing, 80% Rated
Product FAQs
7 answers
What type of panelboards accept the PLA34120U44A circuit breaker?
This PowerPacT P-frame breaker is designed exclusively for Square D I-Line power distribution panelboards and I-Line switchboards.
What does the U44A suffix mean in the PLA34120U44A catalog number?
The U44A suffix indicates the breaker is equipped with a Micrologic 6.0A electronic trip unit. This provides Long-Time, Short-Time, Instantaneous, and Ground-Fault (LSIG) protection functions, plus an integrated ammeter.
How is the PLA34120U44A installed into an electrical system?
It utilizes an I-Line plug-in connection on the line side to mount directly onto the panelboard bus stack. The load side features mechanical lugs that accept four 3/0 AWG to 500 kcmil aluminum or copper conductors.
Can this LSIG circuit breaker be used in an outdoor NEMA 3R I-Line panelboard?
No. Ground-fault capable LSIG breakers require a box extension for the neutral CT assembly. NEMA 3R enclosures cannot be extended, so this breaker must be used in NEMA 1 indoor applications or a separate enclosure.
Are the trip settings on the PLA34120U44A adjustable?
Yes. The Micrologic 6.0A trip unit allows you to adjust the pickup and delay settings for the long-time, short-time, instantaneous, and ground-fault functions to ensure proper system coordination.
Can the trip unit on this P-frame breaker be replaced or upgraded?
Yes. PowerPacT P-frame circuit breakers feature interchangeable Micrologic trip units, allowing you to swap or upgrade the trip unit in the field without replacing the entire breaker frame.
How does the ground-fault function on this breaker operate?
The ground-fault protection monitors the circuit for low-level arcing faults to ground. If a fault exceeds the adjustable pickup setting for the specified delay time, the breaker will trip to prevent equipment damage.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.