Built for overload and short-circuit protection, the Eaton PDG23P0100TFFL is a 100A, 3-pole molded case circuit breaker. Interrupting ratings are 200kA at 240VAC, 100kA at 480VAC and 35kA at 600VAC. This PDG2 series breaker uses a PDE frame, unit mounting and lug terminals. Fixed thermal and fixed magnetic trips provide long-time and instantaneous protection. Approvals include CCC, CE, CSA, IEC, RoHS and UL.
How should I use the 100A rating when selecting the Eaton PDG23P0100TFFL?
The 100A rated current is the starting point for matching the breaker to the circuit's load and conductor ampacity. Coordinate breaker selection with the applicable load calculations and conductor protection requirements.
Which system voltages can I select this breaker for?
The breaker has ratings at 240VAC, 480VAC and 600VAC. Select using the applicable system voltage, then check the interrupting rating at that voltage against the available fault current.
What available fault current can this breaker interrupt?
The interrupting ratings are 200kA at 240VAC, 100kA at 480VAC and 35kA at 600VAC. Use the rating corresponding to the system voltage and ensure it meets or exceeds the available fault current at the installation point.
Can I adjust the thermal or magnetic trip settings?
Both the thermal and magnetic trip settings are fixed. The thermal element provides long-time overload protection, while the magnetic element provides instantaneous protection for high fault currents. Choose this breaker when fixed trip settings suit the circuit's protection requirements.
How do the poles and neutral connection affect circuit selection?
This is a 3-pole breaker for a 3-phase circuit, with no neutral connection. Use its poles for the phase conductors and handle any required neutral connection separately.
What conductor sizes do the lug terminals accept?
The lug terminals accept conductors from 14 AWG through 1/0 AWG. Check both terminal acceptance and conductor ampacity when selecting wiring for the 100A circuit.
What mounting style and dimensions should I plan around?
This unit-mount breaker measures 6.00 in high, 4.12 in wide and 3.50 in deep. Use those dimensions when laying out the mounting location, allowing additional space for conductor routing and termination work.
Which circuit breaker standards apply when reviewing project requirements?
The breaker meets UL 489, CSA C22.2 No. 5 and IEC 60947-2. Use these standards when checking the project's molded case circuit breaker requirements.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.