Eaton / Cutler-HammerEGS3100FFG
Quantity
New
Quantity
Eaton / Cutler-HammerEGS3100FFG
Eaton / Cutler-HammerEGH3100FFG
Eaton / Cutler-HammerEGC3100FFG
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | EGS3100FFB |
| Series | EGS |
| Amperage | 100A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600Y/347VAC, 125/250VDC |
| Phase | 3 |
| AIC Rating | 85kA @ 240VAC, 35kA @ 480VAC, 22kA @ 600Y/347VAC, 35kA @ 125/250VDC |
| Frame Type | EG |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Pow-R-Line Panelboards |
| Wire Gauge | 14-1/0 AWG |
| Max Wire | 1/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator |
|---|---|
| Accessories | Load Side Lugs Included, Mounting Hardware |
| Standards | CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489 |
| Approval | CE, CSA, HACR, IEC, KEMA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Current Limiting, High-Speed Blow-Open Action |
In the Eaton Series G nomenclature, the FFB suffix indicates that the breaker is equipped with a fixed thermal and fixed magnetic trip unit, and it utilizes a bolt-on connection.
The LI designation stands for Long-Time and Instantaneous trip functions. The long-time delay protects the circuit against sustained overloads, while the instantaneous pickup provides immediate tripping during short circuit faults.
The EGS3100FFB is natively a bolt-on circuit breaker designed for Eaton Pow-R-Line panelboards. While EG frame breakers can be adapted for DIN rail mounting using separate accessories, this specific catalog number is configured for bolt-on installation.
Yes, Eaton Series G breakers are backwards compatible with many legacy Cutler-Hammer systems. The EGS3100FFB will fit Cutler-Hammer Pow-R-Line panelboards that accept EG frame bolt-on breakers.
The 600Y/347VAC slash rating indicates this breaker is designed for use in solidly grounded wye systems where the line-to-line voltage is 600V and the line-to-neutral voltage is 347V. It is not suitable for 600V ungrounded or corner-grounded delta systems.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.