Built for circuit protection against overloads and short circuits, the Eaton PDG23P0020TFFL molded case circuit breaker is rated 20A and 600VAC with 3 poles. Its interrupting rating is 100kAIC at 480VAC. The Power Defense PDG2 frame uses panel mounting and a standard load side lug. Fixed thermal and fixed magnetic trips provide long-time and instantaneous protection. Approvals include CSA, CCC, IEC, UL and CE.
How should I use the 20A rating when selecting the Eaton PDG23P0020TFFL?
The 20A rated current guides selection of the breaker's overcurrent protection for the circuit. Coordinate that rating with the calculated load, conductor ampacity and applicable installation requirements.
How does the 600VAC rating guide voltage selection?
Select this breaker for an AC circuit whose system voltage is within its 600VAC rating. Check voltage and interrupting ratings separately, since the interrupting rating applies at a particular voltage.
How do I apply the 100kAIC interrupting rating at 480VAC?
For a 480VAC installation, compare the available fault current at the installation point with the breaker's 100kAIC interrupting rating. Select it where the available fault current does not exceed that rating.
How does the thermal-magnetic trip work, and can I adjust it?
The thermal-magnetic trip combines long-time overload protection with instantaneous response to high fault current. Both the thermal and magnetic settings are fixed, so select the breaker with the required current rating rather than planning field trip adjustments.
What conductor sizes can I use at the load-side connection?
The conductor range is 14-1/0 AWG, and the load-side connection uses a standard lug. Select a conductor within that range, then size it for the circuit load and applicable installation requirements.
How should I use the phase and pole ratings when selecting this breaker?
The Eaton PDG23P0020TFFL has three poles and a three-phase rating. Check both the phase count and pole count against the circuit design rather than selecting by current and voltage alone.
What body dimensions should I use when planning the installation layout?
The breaker body measures 6 in high, 4.12 in wide and 3.5 in deep. Use these dimensions to lay out the installation space, allowing additional room for conductor routing and terminal access.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.