Engineered for industrial power distribution, the Eaton FDB2040L is a 2-pole, 40A molded case circuit breaker from the proven Series C family. It delivers robust thermal-magnetic protection with fixed long-time and instantaneous (LI) trip functions. Designed for unit mount applications, this F-Frame breaker installs into Eaton enclosures, switchboards, and motor control centers. It features a 14 kAIC rating at 480VAC, making it an excellent choice for demanding commercial environments.
What does the "L" in the FDB2040L catalog number indicate?
The "L" suffix indicates that the circuit breaker comes complete with factory-installed line and load lugs.
Can I install the FDB2040L in a standard loadcenter?
No, the FDB2040L is a unit-mount, bolt-on F-Frame breaker designed for industrial switchboards, motor control centers, and specific F-Frame enclosures. It is not compatible with standard residential plug-on or bolt-on loadcenters like Type BR or Type CH.
How is the FDB2040L wired for 250VDC applications?
While rated for 250VDC at 10kAIC, DC applications often require multiple poles to be wired in series to safely break the DC arc. The specific wiring configuration depends on whether the system is grounded or ungrounded. Always consult Eaton's DC application guidelines and local codes.
Can the FDB2040L be reverse fed?
Yes, standard Eaton FDB thermal-magnetic breakers can be reverse fed (back-fed) as long as they do not have factory "Line" and "Load" markings. When used to back-feed a panel, a retaining bracket or hold-down kit must be installed to secure the breaker per NEC requirements.
Does the FDB2040L provide ground fault or arc fault protection?
No, this is a standard thermal-magnetic circuit breaker equipped with fixed long-time and instantaneous (LI) trip functions. It does not provide GFCI or AFCI protection.
What is the torque specification for the lugs on the FDB2040L?
For the standard 14 AWG to 1/0 AWG lugs, the required torque depends on the wire size. Typically, 14 to 10 AWG requires 35 lb-in, 8 AWG requires 40 lb-in, 6 to 4 AWG requires 45 lb-in, and 3 to 1/0 AWG requires 50 lb-in. Always verify the exact torque values printed on the breaker nameplate or lug before terminating.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 2 reviews.