Part of the Series C family, the Eaton HFDE308035L is an 80A, 3-pole molded case circuit breaker designed for commercial and industrial distribution. This unit-mount F-Frame breaker installs into Eaton Pow-R-Line C panelboards, switchboards, and motor control centers. It accepts 14-1/0 AWG wire and serves as a reliable component for facility upgrades.
What trip functions are included in the HFDE308035L?
This breaker is equipped with a Digitrip 310+ electronic trip unit featuring LSG protection. This provides adjustable Long-Time, Short-Time, and Ground Fault protection. The 35 suffix indicates an I2t response for the short delay and a flat response for ground fault protection.
Is the ground fault pickup adjustable on this 80A breaker?
Yes. The ground fault pickup on the 310+ LSG trip unit can be adjusted from 0.2x to 1.0x of the maximum frame rating. It also features three ground fault time delay settings: Instantaneous, 120 ms, and 300 ms.
What does the H in the HFDE308035L catalog number signify?
The H designates this as a high-interrupting capacity breaker within the F-frame family. It provides a maximum interrupting rating of 100kA at 240V AC, 65kA at 480V AC, and 25kA at 600V AC.
What wire sizes are compatible with the HFDE308035L terminals?
The L suffix in the catalog number indicates that the breaker comes with factory-installed line and load side lugs. These standard lugs accept 14 AWG to 1/0 AWG copper or aluminum conductors.
Which panelboards accept the HFDE308035L circuit breaker?
This Series C F-frame breaker is designed for installation in Eaton Pow-R-Line C panelboards, legacy Series C panelboards, switchboards, and motor control centers.
Can this Eaton breaker replace legacy Westinghouse models?
Yes. Eaton acquired the Westinghouse distribution equipment line, and current Eaton Cutler-Hammer Series C breakers are direct replacements for legacy Westinghouse Series C breakers with matching frame sizes and specifications.
Does the electronic trip unit in the HFDE308035L feature thermal memory?
Yes. The integrated electronic sensing mechanism includes a thermal memory feature that replicates the thermal heating and cooling of the load during overload conditions, preventing equipment damage from repeated overcurrent events.
Can I field-install internal accessories like auxiliary switches in this breaker?
No. For Series C F-frame breakers, internal accessories such as shunt trips, alarm switches, or auxiliary contacts must be factory-installed to maintain the breaker seal and UL label.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.