Eaton / Cutler-Hammer HND3800T36W Molded Case Circuit Breaker

  • 800A
  • 3 Pole
  • Panel Mount
Eaton / Cutler-Hammer HND3800T36W
Molded Case Circuit Breaker
Brand Eaton / Cutler-Hammer
SKU HND3800T36W
Select Item Condition
Earn 14295 SuperPoints
  • 800A
  • 3 Pole
  • Panel Mount

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Eaton / Cutler-Hammer HND3800T36W - 800A 3 Pole Molded Case Circuit Breaker

New

$14,295.14 In Stock

Quantity

Description

Engineered for commercial and industrial applications, the Eaton HND3800T36W is an 800A, 3-pole molded case circuit breaker from the Series C N-Frame family. This panel-mount breaker installs into Eaton Series C panelboards, switchboards, and motor control centers. It serves as a replacement for older installations, though it is replaced by the NGH308036E for Series G retrofits. Equipped with a Digitrip 310 electronic trip unit, it provides adjustable LSIG protection and is HACR rated.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Part Number HND3800T36W
Series HND
Amperage 800A
Poles 3
Mounting Style Panel Mount
Voltage 240VAC, 480VAC, 600VAC
Phase 3
AIC Rating 100kA @ 240VAC, 65kA @ 480VAC, 35kA @ 600VAC
Fit and installation
Terminal Type Lugs
For Use With Eaton Series C Panelboards, Switchboards, Motor Control Centers
Protection and operation
Trip Technology Electronic Trip
Trip Function Code LSIG
Trip Function Long-Time, Short-Time, Instantaneous, Ground Fault
Trip Adjustability Adjustable
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Rating Plugs, Lug Kits
Accessories Without Terminals
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval CE, CSA, HACR, UL
Temp Rating 40C
Construction Features HACR Rated, Reverse Feed, 80% Rated

Product FAQs

8 answers
What is the difference between the HND3800T36W and the standard ND3800T36W?

The HND prefix indicates this is the high-interrupting version of the Series C N-Frame breaker. It provides a 65kA interrupting capacity at 480V AC, compared to the standard ND version which has a lower AIC rating. Both share the same physical dimensions and N-Frame accessories.

Does the HND3800T36W require a rating plug to operate?

Yes. Like all Eaton Series C N-Frame breakers with Digitrip 310 electronic trip units, this breaker requires a compatible rating plug to establish its maximum continuous current rating. The breaker will not function properly without the correct rating plug installed.

Do I need an external neutral sensor for the ground fault function to work?

An external neutral current sensor, or neutral CT, is only required if you are installing this breaker in a 4-wire system. For 3-wire systems, the internal sensors are sufficient to detect ground faults, and a separate neutral sensor is not needed.

What do the LSIG functions on the Digitrip 310 trip unit allow me to adjust?

The LSIG designation means the trip unit provides adjustable Long-Time, Short-Time, Instantaneous, and Ground Fault protection. This allows you to fine-tune the breaker time-current curve to coordinate with other protective devices in your electrical system and prevent nuisance tripping.

Can I install this 800A HND breaker in an older Cutler-Hammer switchboard?

Yes, the HND3800T36W is fully compatible with Eaton and legacy Cutler-Hammer Series C panelboards, switchboards, and motor control centers designed to accept N-Frame circuit breakers.

Can the Digitrip 310 trip unit in this N-Frame breaker be replaced in the field?

No. For Eaton Series C N-Frame circuit breakers, the electronic trip unit is built in as an integral part of the breaker frame and is not field-replaceable. If the trip unit fails, the entire circuit breaker must be replaced.

Is the HND3800T36W rated for reverse feed applications?

Yes, Eaton Series C molded case circuit breakers, including the N-Frame HND series, are suitable for reverse feed use.

Is this breaker suitable for 100 percent continuous operation?

No. Standard Eaton Series C breakers like the HND3800T36W are standard 80 percent rated. Breakers rated for 100 percent continuous operation would have a "C" prefix in the catalog number, such as CHND.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.