Eaton's QCHW3020H is a 20-amp, three-pole miniature circuit breaker belonging to the proven Quicklag product line. Engineered for commercial environments, it provides dependable thermal-magnetic protection for three-phase equipment. This unit mount breaker features a cable-in/cable-out design, allowing it to be installed in control panels or standalone enclosures. With an interrupting rating of 22 kAIC at 240VAC, this device handles high fault currents safely and is HACR rated.
Control Panels, Enclosures, DIN Rail (with adapter)
Wire Gauge
14-10 AWG (Al/Cu)
Max Wire
10 AWG
Min Wire
14 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Fixed
Standards and features
Available Options
Padlock Attachment
Accessories
Line and Load Lugs Included
Standards
CSA C22.2 No. 5, HACR, UL 489
Approval
CSA, UL
Temp Rating
40C
Construction Features
HACR Rated, Non-Interchangeable Trip
Product FAQs
6 answers
What are the recommended terminal torque specifications for the QCHW3020H?
For the accepted 14 to 10 AWG wire range, the box lug terminals should be torqued to 20 in-lbs. Always use 60/75 degree Celsius rated copper or aluminum conductors to ensure a secure and compliant connection.
Can I install the QCHW3020H in a standard residential load center?
No. The QCHW3020H is a unit mount, cable-in/cable-out breaker designed for OEM control panels, enclosures, and DIN rail applications. It is not a plug-on breaker and will not fit in standard residential load centers like the Eaton CH or BR series.
Is the QCHW3020H rated for heating, air conditioning, and refrigeration equipment?
Yes, Eaton Quicklag miniature circuit breakers in this amperage range are HACR rated. This makes the breaker suitable for protecting dedicated HVAC circuits and motor loads.
How is the QCHW3020H circuit breaker mounted?
This breaker features a unit mount design for feed-thru installations. It can be front-mounted in compatible OEM control panels and enclosures, or it can be mounted on a standard 35mm DIN rail when paired with the appropriate Eaton mounting adapter.
What is the difference between Eaton QC and QCHW series breakers?
Both are part of the Eaton Quicklag family of cable-in/cable-out miniature breakers. The primary difference is the short circuit interrupting capacity. Standard QC breakers typically feature a 10kAIC rating, while QCHW breakers are built with a higher 22kAIC rating.
Does the QCHW3020H have an adjustable trip setting?
No, this breaker features a fixed thermal magnetic trip unit with long-time and instantaneous protection functions. The trip settings are factory calibrated and cannot be adjusted in the field.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.