Eaton / Cutler-Hammer BRHH290 Miniature Circuit Breaker

  • 90A
  • 2 Pole
  • Plug-On
Eaton / Cutler-Hammer BRHH290
Miniature Circuit Breaker
Brand Eaton / Cutler-Hammer
SKU BRHH290
Select Item Condition
Earn 243 SuperPoints
  • 90A
  • 2 Pole
  • Plug-On

Quantity

Bulk Pricing
Send your parts list for a volume quote.
Eaton / Cutler-Hammer BRHH290 - 90A 2 Pole Miniature Circuit Breaker

Eaton / Cutler-Hammer BRHH290 - 90A 2 Pole Miniature Circuit Breaker

New

$243.60 In Stock

Quantity

Similar Items

Description

Supplying 90 amps of thermal-magnetic protection, the Eaton BRHH290 safeguards heavy-duty residential and commercial electrical circuits. This 2-pole plug-on breaker is specifically designed to fit Eaton Type BR load centers. It features box lug terminals that accept #4 to 1/0 AWG copper or aluminum wire, ensuring a solid connection. The 42kAIC interrupting rating makes it ideal for locations requiring high short-circuit protection. It also includes a common trip function and HACR rating.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Series BRHH
Amperage 90A
Poles 2
Mounting Style Plug-On
Voltage 120/240VAC
Phase 1
AIC Rating 42kA @ 120/240VAC
Fit and installation
Frame Type BR
Terminal Type Box Lugs
For Use With Eaton Type BR Load Centers
Wire Gauge 4-1/0 AWG (Cu/Al)
Max Wire 1/0 AWG
Min Wire 4 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Padlock Attachment, Handle Lock
Standards UL 489, Federal Specification W-C376, HACR
Approval UL
Temp Rating 60C to 75C
Construction Features Common Trip, HACR Rated, High Interrupting Capacity

Product FAQs

5 answers
Which load centers are compatible with the BRHH290 circuit breaker?

This breaker is designed for use in Eaton Type BR load centers. It is also UL approved for installation in legacy Westinghouse, Challenger, Bryant, and Cutler-Hammer panels that are listed to accept Type BR breakers.

What is the difference between Eaton BR, BRH, and BRHH breakers?

The suffix indicates the short-circuit interrupting rating. Standard BR breakers are rated for 10 kAIC, BRH models are rated for 22 kAIC, and BRHH models like this one feature a high interrupting rating of 42 kAIC for systems with higher available fault current.

Can I use the BRHH290 to replace a standard BR290 or BRH290?

Yes. The BRHH290 shares the same physical 1-inch per pole plug-on footprint as the standard BR290 (10 kAIC) and BRH290 (22 kAIC). It can safely replace them while providing a higher 42 kAIC interrupting capacity, provided the panel is rated to accept 90-amp branch breakers.

Are the box lugs on the BRHH290 rated for aluminum wire?

Yes, the terminal lugs are dual-rated for both copper (Cu) and aluminum (Al) conductors. When terminating aluminum wire, it is standard practice to apply an oxide-inhibiting joint compound to prevent corrosion and maintain a reliable connection.

Does this breaker provide GFCI or AFCI protection?

No. The BRHH290 is a standard thermal-magnetic circuit breaker providing overload and short-circuit protection. It does not include ground fault (GFCI) or arc fault (AFCI) protection circuitry.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.