Skip to main content
Expedited shipping available at checkout

Eaton / Cutler-Hammer BJH2125 Molded Case Circuit Breaker

  • 125A
  • 2 Pole
  • Plug-On
Eaton / Cutler-Hammer BJH2125
Molded Case Circuit Breaker
Brand Eaton / Cutler-Hammer
SKU BJH2125
Select Item Condition
Earn 1253 SuperPoints
  • 125A
  • 2 Pole
  • Plug-On

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Eaton / Cutler-Hammer BJH2125 - 125A 2 Pole Molded Case Circuit Breaker

New

$1,253.96 In Stock

Quantity

Description

Designed for residential and commercial applications, the Eaton BJH2125 operates as a 125-amp main or branch circuit breaker. The thermal-magnetic design provides reliable long-time and instantaneous trip functions. This two-pole breaker requires four pole spaces and installs into compatible Eaton Type BR load centers. It supports reverse feed configurations for versatile panel arrangements. With an upgraded 22kAIC rating at 120/240VAC, it offers superior fault current handling capabilities.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Part Number BJH2125
Series BJH
Amperage 125A
Poles 2
Mounting Style Plug-On
Voltage 120/240VAC
Phase 1
AIC Rating 22kA @ 120/240VAC
Fit and installation
Terminal Type Lugs
For Use With Eaton Type BR Load Centers
Wire Gauge 2 AWG - 300 kcmil (Cu/Al)
Max Wire 300 kcmil
Min Wire 2 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed
Standards and features
Accessories Lugs Included
Standards CSA C22.2 No. 5, Federal Specification W-C375, UL 489
Approval CSA, UL
Temp Rating 60C to 75C
Construction Features Common Trip, High Interrupting Capacity, Main Breaker, Reverse Feed

Product FAQs

5 answers
How many panel spaces does the BJH2125 require?

This 2-pole breaker requires four 1-inch spaces in an Eaton Type BR load center. It mounts across the busbar, occupying two spaces on the left side and two spaces on the right side.

Can the Eaton BJH2125 be used as a main breaker?

Yes, it is frequently installed as a 125A main breaker in compatible Eaton BR load centers and residential meter stacks. It can also be used as a sub-feed breaker to supply power to a downstream subpanel.

What is the difference between the Eaton BJ2125 and BJH2125 circuit breakers?

The primary difference is their short-circuit interrupting capacity. The standard BJ2125 is rated for 10 kAIC, whereas the BJH2125 features an upgraded 22 kAIC rating for systems with higher available fault current.

Will the BJH2125 fit in older Westinghouse or Bryant panels?

Yes, Eaton manufactures the BR and BJH series as direct, UL-listed replacements for legacy Cutler-Hammer, Westinghouse, and Bryant load centers that originally accepted Type BR plug-on breakers.

Can the BJH2125 be reverse fed when used as a main breaker?

Yes, this breaker supports reverse feed configurations. When installing it as a backfed plug-on main breaker in a load center, you must use a manufacturer-approved breaker hold-down kit to comply with National Electrical Code (NEC) requirements.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.