Belonging to Eaton's CV frame family, the CVH3150 is a 3-pole, 150A molded case circuit breaker. It functions primarily as a tenant main breaker for commercial and industrial applications. This unit mount breaker installs into Eaton Type ECC enclosures and includes line and load lugs. It serves as a direct replacement for legacy CHH3150 and CCH3150 breakers. Rated for 100 kAIC at 240V, it safely handles high fault currents. It features fixed thermal-magnetic trip settings and is HACR rated.
Can the CVH3150 be installed in systems with lower fault current requirements?
Yes. With a maximum interrupting rating of 100kAIC at 240VAC, this breaker safely exceeds the requirements for systems needing 10kAIC, 22kAIC, 42kAIC, or 65kAIC protection.
Are the trip settings on the CVH3150 adjustable?
No. This breaker is equipped with a thermal-magnetic trip unit featuring fixed thermal (Long-Time) and fixed magnetic (Instantaneous) settings. They cannot be field-adjusted.
Do I need to purchase separate lugs for installation?
No. The breaker includes factory-installed line and load lugs designed to accept 6 AWG through 4/0 AWG copper or aluminum (Cu/Al) conductors.
What type of enclosure is required for a standalone installation of this breaker?
When not installed directly inside a panelboard or meter stack, the CVH3150 is designed to be mounted in Eaton Type ECC enclosures.
Can the CVH3150 be used as a tenant main breaker?
Yes. Eaton CV-frame breakers, including the CVH3150, are frequently used as tenant main breakers in multi-metering equipment and compatible panelboards.
What is the difference between the CV3150 and the CVH3150?
Both are 150A, 3-pole breakers in the Eaton CV frame family, but they have different interrupting ratings. The CV3150 is rated for 65kAIC, whereas the CVH3150 provides a higher 100kAIC rating.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.