Eaton / Cutler-HammerEGS2040FFB
Quantity
New
Quantity
Eaton / Cutler-HammerEGS2040FFB
Eaton / Cutler-HammerEGS3040FFG
Eaton / Cutler-HammerEGH3040FFG
Eaton / Cutler-HammerEGC3040FFG
| Brand | Eaton / Cutler-Hammer |
|---|---|
| Part Number | EGS3040FFB |
| Series | EGS |
| Amperage | 40A |
| Poles | 3 |
| Mounting Style | Bolt-On |
| Voltage | 240VAC, 480VAC, 600Y/347VAC, 125/250VDC |
| Phase | 3 |
| AIC Rating | 85kA @ 240VAC, 35kA @ 480VAC, 22kA @ 600Y/347VAC, 35kA @ 125/250VDC |
| Frame Type | EG |
|---|---|
| Terminal Type | Lugs |
| For Use With | Eaton Pow-R-Line Panelboards |
| Wire Gauge | 14-1/0 AWG |
| Max Wire | 1/0 AWG |
| Min Wire | 14 AWG |
| Trip Technology | Thermal Magnetic |
|---|---|
| Trip Function Code | LI |
| Trip Function | Long-Time, Instantaneous |
| Trip Adjustability | Fixed Thermal, Fixed Magnetic |
| Available Options | Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator |
|---|---|
| Accessories | Load Side Lugs Included, Mounting Hardware |
| Standards | CSA C22.2 No. 5, IEC 60947-2, UL 489 |
| Approval | CE, CSA, IEC, KEMA, UL |
| Temp Rating | 40C |
| Construction Features | HACR Rated, Current Limiting, High-Speed Blow-Open Action |
The EGS3040FFB is a bolt-on branch breaker designed specifically for Eaton Pow-R-Line distribution panelboards. It connects directly to the panelboard bus using its line-side bolt-on tabs.
Both are 40A, 3-pole Series G EG-frame breakers with identical trip units and interrupting ratings. The difference is the termination. The EGS3040FFB has bolt-on line tabs for panelboard mounting, while the EGS3040FFG features standard wire lugs on both the line and load sides.
The EGS3040FFB is a bolt-on breaker. The B suffix in the catalog number designates bolt-on line tabs for Pow-R-Line panelboards. While standard EG-frame breakers can sometimes use DIN rail adapters, this specific variant requires a bolted bus connection.
The load-side lugs on the EGS3040FFB accept wire gauges from 14 AWG up to 1/0 AWG. Ensure you torque the terminals to the manufacturer specifications found on the breaker label.
No. This breaker uses a fixed thermal and fixed magnetic trip unit. Both the long-time overload and instantaneous short-circuit trip functions are factory-set for 40 amps and cannot be modified in the field.
Yes, this thermal-magnetic breaker is rated for DC applications up to 125/250VDC, where it provides a 35kAIC interrupting rating.
Earn points on eligible purchases and redeem them at checkout.
100 SuperPoints = $1 off.
Your purchase includes 60 days of SuperBreakers warranty coverage.
Add a 1-year warranty extension in your cart.
We source obsolete and hard-to-find parts every day.
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.