Built for demanding environments, the FAZ-B10/2-NA provides robust current-limiting protection. This 10A, two-pole miniature circuit breaker handles low inrush loads. The unit mounts securely onto standard DIN rail systems and integrates into industrial control panels. Its box lug terminals accommodate 18-6 AWG wiring. Featuring a B-curve trip characteristic, it delivers a 10kAIC rating at 480Y/277VAC. The breaker includes a trip-free mechanism and is UL 489 listed.
Is the FAZ-B10/2-NA rated for branch circuit protection?
Yes, the FAZ-B10/2-NA is UL 489 listed, making it suitable for branch circuit protection. This is a key difference from UL 1077 supplementary protectors. It can be used for internal or external receptacles, motor control circuits, and HACR equipment.
What does the B-curve trip characteristic mean for this breaker?
The B-curve profile means the breaker is designed to trip instantaneously at 3 to 5 times the rated current. This makes it ideal for applications with low inrush currents, such as sensitive control circuits, PLC I/O points, and resistive loads.
Can the FAZ-B10/2-NA be reverse fed?
Yes, this miniature circuit breaker supports reverse feed wiring, allowing for flexible installation in industrial control panels and DIN rail systems.
Is this breaker suitable for switching fluorescent lighting loads?
Yes, the FAZ-B10/2-NA carries an SWD (Switching Duty) rating, meaning it is approved for switching fluorescent lighting loads on a regular basis.
Does this breaker have a trip-free mechanism?
Yes, it features a trip-free design. The breaker will still trip during an overcurrent or short-circuit event even if the handle is physically held in the ON position.
Is the FAZ-B10/2-NA a current-limiting breaker?
Yes, it features a current-limiting design that interrupts fault currents within one half-cycle. This reduces the peak let-through energy, providing superior protection against damage for downstream circuit components.
Can I use this UL 489 breaker in place of a UL 1077 supplementary protector?
Yes, a UL 489 branch circuit breaker like the FAZ-B10/2-NA can generally be used in applications that only require UL 1077 supplementary protection. However, a UL 1077 device cannot be used where UL 489 branch protection is required.
Does this breaker include a visual status indicator?
Yes, the FAZ-NA series features a red and green contact position indicator on the front of the device to clearly show the breaker's operational status.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 2.0 out of 5 based on 2 reviews.