Built for demanding industrial environments, this 40A two-pole miniature circuit breaker provides robust branch protection for highly inductive loads. The D-curve trip characteristic allows it to handle the significant inrush currents generated by motors and transformers without nuisance tripping. It mounts seamlessly onto standard 35mm DIN rail systems in commercial control panels. This component is an exact drop-in replacement for the discontinued WMZT2D40. Rated at 10 kAIC at 240VAC.
What does the D trip curve signify on the FAZ-D40/2-NA?
The D-curve indicates a magnetic trip point of 10 to 20 times the rated current. This makes it ideal for highly inductive loads with significant inrush currents, such as motors, transformers, and solenoid valves, preventing nuisance tripping during startup.
Can I use the FAZ-D40/2-NA to replace a discontinued WMZT2D40 breaker?
Yes, the Eaton FAZ-D40/2-NA is an exact drop-in replacement for the obsolete WMZT2D40 miniature circuit breaker.
Is the FAZ-D40/2-NA rated for branch circuit protection?
Yes, the -NA suffix indicates this breaker is UL 489 listed for branch circuit protection, unlike standard UL 1077 supplementary protectors. It is also CSA C22.2 No. 5 and IEC 60947-2 compliant.
What type of DIN rail is required to mount this 2-pole breaker?
The FAZ-D40/2-NA mounts directly onto a standard 35mm DIN rail using a spring clip. The two-pole module has a total width of approximately 35mm, or 17.5mm per pole.
Does the FAZ-D40/2-NA feature a trip-free mechanism?
Yes, it utilizes a trip-free design. The breaker will still trip internally during an overload or short circuit even if the handle is physically held in the ON position.
How can I visually verify the contact status of this breaker?
The breaker features a color-coded indicator on the front face that provides immediate visual confirmation of the contact position. It displays red when the contacts are closed (ON) and green when they are open (OFF).
Is the Eaton FAZ-D40/2-NA a current-limiting breaker?
Yes, it features a current-limiting design that provides fast short-circuit interruption. This reduces the peak let-through energy, offering superior protection for downstream circuit components.
Can the FAZ-D40/2-NA be reverse fed?
Yes, power to this miniature circuit breaker can be fed from either the line or the load side, offering flexible wiring options in control panels.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.