Designed for demanding industrial environments, the Eaton FAZ-D6/2-NA is a 6A miniature circuit breaker built to handle highly inductive loads. The two-pole unit provides essential protection where significant startup inrush currents are common. This breaker installs onto standard 35mm DIN rail and accepts 18-6 AWG wire via secure box lug terminals. It is compatible with field-installable accessories like auxiliary switches.
Current Limiting, HACR Rated, Reverse Feed, Trip-Free Mechanism, Visual Trip Indicator, Common Trip
Product FAQs
7 answers
What applications are best suited for the D-curve trip characteristic on the FAZ-D6/2-NA?
The D-curve magnetic trip is calibrated to activate between 10 and 20 times the rated current. This high inrush tolerance makes it ideal for highly inductive loads like motors, transformers, and switched-mode power supplies.
Does the FAZ-D6/2-NA qualify for branch circuit protection?
Yes, the -NA suffix indicates this breaker is UL 489 listed, making it fully approved for branch circuit protection in North America, rather than just supplementary protection (UL 1077).
What size DIN rail is required for installing the FAZ-D6/2-NA?
This miniature circuit breaker is designed to snap directly onto a standard 35mm DIN rail, which is typical for industrial control panels.
How many conductors can be terminated in the box lugs of the FAZ-D6/2-NA?
The terminals are rated for either a single conductor between 18 AWG and 6 AWG, or two conductors between 18 AWG and 10 AWG.
Can the FAZ-D6/2-NA be used in reverse-feed applications?
Yes, Eaton FAZ-NA series miniature circuit breakers are reverse-feed capable, allowing line and load power connections to be made at either the top or bottom terminals without derating.
Is the FAZ-D6/2-NA compatible with standard lockout/tagout (LOTO) devices?
Yes, the toggle actuator on FAZ series breakers can be secured using standard DIN rail breaker lockout attachments to ensure safe isolation during maintenance.
What is the difference between the FAZ-D6/2-NA and the standard FAZ-D6/2?
The FAZ-D6/2-NA is the North American version, which is UL 489 listed for branch circuit protection. The standard FAZ-D6/2 without the -NA suffix is typically UL 1077 recognized for supplementary protection only.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 2.0 out of 5 based on 2 reviews.