Part of the Series C family, the Eaton FDC2125 is a 2-pole, 125A molded case circuit breaker. This F-frame device provides robust protection for 600VAC or 250VDC systems. Designed for versatile application, it mounts into Eaton Series C panelboards, switchboards, and motor control centers. It is reverse feed capable and includes load-side lugs. With a 100kAIC rating at 480V, the current-limiting design minimizes fault energy. Fixed thermal and magnetic trip units ensure precise LI protection.
CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489
Approval
CSA, UL
Temp Rating
40C
Construction Features
HACR Rated, Current Limiting, Reverse Feed, Non-Interchangeable Trip
Product FAQs
8 answers
What is the difference between the Eaton FD, HFD, and FDC circuit breakers?
The primary difference is the interrupting capacity. The FD is the standard interrupting breaker, the HFD is high interrupting, and the FDC is the extra-high interrupting, current-limiting version. All three share the same physical F-Frame dimensions and mount in the same Series C panelboards.
Is the FDC2125 circuit breaker current limiting?
Yes, the FDC series is a current-limiting molded case circuit breaker. Its design minimizes let-through energy during a fault, providing enhanced protection for downstream equipment.
Can the FDC2125 be reverse fed?
Yes, Eaton Series C F-Frame breakers, including the FDC2125, are reverse feed capable. They can be wired with the line connections on either the top or bottom terminals.
What wire sizes are accepted by the lugs on the FDC2125?
The standard lugs accept copper or aluminum wire ranging from 4 AWG to 4/0 AWG. Ensure proper torque specifications are followed during installation as outlined on the breaker faceplate.
Is this breaker suitable for DC voltage applications?
Yes, the FDC2125 is rated for use in DC systems up to 250VDC, with a direct current interrupting rating of 22kAIC.
What types of enclosures or panels are compatible with this breaker?
This unit-mount breaker is designed for use in Eaton Series C panelboards, switchboards, and motor control centers. It bolts directly to the chassis or mounting pan.
Does the FDC2125 have an interchangeable trip unit?
No, this breaker features a non-interchangeable, fixed thermal-magnetic trip unit. The long-time and instantaneous trip functions are factory set and cannot be modified or swapped.
Is the FDC2125 HACR rated?
Yes, this breaker is HACR rated, meaning it is approved for use with heating, air conditioning, and refrigeration equipment that requires this specific designation.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 2 reviews.