Rated for 225 amps, this high-performance F-Frame breaker incorporates a fully adjustable LSIG electronic trip unit for maximum system coordination. It fastens into Eaton Series C panelboards, Pow-R-Line switchboards, and commercial motor control centers. Offering a formidable 100kAIC rating at 480VAC, the HACR-rated component includes load-side lugs and delivers reliable true RMS sensing for complex electrical networks.
What panelboards and enclosures are compatible with the FDCE322536?
This F-frame breaker is designed for use in Eaton Series C panelboards, Pow-R-Line panelboards, switchboards, and commercial motor control centers.
What does the 36 suffix in the FDCE322536 catalog number indicate?
The 36 suffix designates that the breaker is equipped with an electronic LSIG trip unit, providing adjustable Long-Time, Short-Time, Instantaneous, and Ground-Fault protection functions.
What type of sensing technology does the FDCE322536 use?
It utilizes a Digitrip 310+ electronic trip unit with true RMS sensing, which provides accurate protection and thermal memory independent of ambient temperature.
Is the Eaton FDCE322536 HACR rated?
Yes, all Eaton F-Frame circuit breakers, including the FDCE322536, are HACR rated for use with heating, air conditioning, and refrigeration equipment.
What wire sizes are accepted by the standard lugs on the FDCE322536?
The standard load-side lugs accept wire gauges from 4 AWG to 4/0 AWG and are compatible with both copper and aluminum conductors.
Does the ground-fault function on the FDCE322536 require additional components?
When installed in a 3-phase, 4-wire system, the LSIG trip unit requires a separately ordered neutral current sensor to properly detect ground faults.
Can the FDCE322536 be used in reverse feed applications?
Yes, the patented contact design of this Series C breaker makes it suitable for reverse feed applications.
How does the FDCE322536 respond to high-level short circuits?
The breaker features a patented contact design with high-speed blow-open action, which rapidly clears faults to provide superior protection for downstream equipment.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.