Skip to main content
Expedited shipping available at checkout

Eaton / Cutler-Hammer FDE316033 Molded Case Circuit Breaker

  • 160A
  • 3 Pole
  • Panel Mount
Eaton / Cutler-Hammer FDE316033
Molded Case Circuit Breaker
Brand Eaton / Cutler-Hammer
SKU FDE316033
Select Item Condition
Earn 2456 SuperPoints
  • 160A
  • 3 Pole
  • Panel Mount

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Eaton / Cutler-Hammer FDE316033 - 160A 3 Pole Molded Case Circuit Breaker

New

$2,456.30 In Stock

Quantity

Description

Providing advanced microprocessor-based protection, the Eaton FDE316033 is a 3-pole, 160A molded case circuit breaker from the Series C F-Frame lineup. This panel mount MCCB integrates seamlessly into Eaton Series C panelboards, switchboards, and motor control centers, coming standard with load side lug terminals. Rated for 35 kAIC at 480VAC, it features a Digitrip 310+ electronic trip unit configured with adjustable Long-Time and Short-Time (LS) protection functions and true RMS sensing.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Part Number FDE316033
Series FDE
Amperage 160A
Poles 3
Mounting Style Panel Mount
Voltage 240VAC, 480VAC, 600VAC
Phase 3
AIC Rating 65kA @ 240VAC, 35kA @ 480VAC, 18kA @ 600VAC
Electrical ratings
Amperage Range 60-160A
Fit and installation
Frame Type F
Terminal Type Lugs
For Use With Eaton Series C Panelboards, Switchboards, MCCs
Wire Gauge 4 AWG - 4/0 AWG (Cu/Al)
Max Wire 4/0 AWG
Min Wire 4 AWG
Protection and operation
Trip Technology Electronic Trip
Trip Function Code LS
Trip Function Long-Time, Short-Time
Trip Adjustability Adjustable
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, Line Side Lugs
Accessories Load Side Terminals
Standards CSA C22.2 No. 5, NEMA AB-1, UL 489
Approval CSA, UL
Temp Rating 40C
Construction Features HACR Rated, True RMS Sensing

Product FAQs

9 answers
What does the "33" suffix indicate in the FDE316033 catalog number?

The "33" suffix indicates that the breaker is equipped with a Digitrip 310+ electronic trip unit featuring Long-Time and Short-Time (LS) protection functions.

Does the FDE316033 require a separate rating plug to set the amperage?

No, the Digitrip 310+ electronic trip unit does not require a separate rating plug. It features selectable dial settings to adjust the amperage rating directly on the breaker face.

Can I install the FDE316033 in a standard residential load center?

No, the FDE316033 is a commercial and industrial molded case circuit breaker designed specifically for Eaton Series C panelboards, switchboards, and motor control centers (MCCs). It will not fit in standard residential load centers.

Can the Eaton FDE316033 circuit breaker be reverse fed?

Yes, Eaton Series C electronic F-frame breakers, including the FDE316033, are suitable for reverse feed applications.

Can I use the FDE316033 to replace an older thermal-magnetic FD3160 breaker?

Yes, the FDE316033 shares the same physical F-frame footprint as the thermal-magnetic FD3160. It serves as a direct physical replacement while upgrading the circuit protection to a solid-state electronic trip unit.

Are the standard lugs on the FDE316033 rated for aluminum wire?

Yes, the factory-installed lugs accept 4 AWG to 4/0 AWG wire and are dual-rated for both copper (Cu) and aluminum (Al) conductors.

How do I adjust the trip settings on the FDE316033?

The Digitrip 310+ trip unit features adjustable dials on the face of the breaker. These dials allow you to configure the Long-Time and Short-Time (LS) pickup and delay settings to match your specific load requirements.

Does the FDE316033 include ground fault protection?

No, the "33" suffix indicates Long-Time and Short-Time (LS) functions only. For ground fault protection, you would need a breaker with an LSG or LSIG trip unit, such as one with a "35" or "36" suffix.

What is the difference between the FDE316033 and the HFDE316033?

The primary difference is the short-circuit interrupting capacity. The standard FDE316033 is rated for 35kAIC at 480VAC, while the HFDE316033 is the high-interrupting version rated for 65kAIC at 480VAC. Both share the same physical dimensions and electronic trip unit.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.