Belonging to the Series C lineup, the HFDDC3200L is a 3-pole, 200A molded case circuit breaker engineered for industrial and solar/PV applications. It delivers reliable power distribution for demanding environments, including solar combiner boxes. This F-Frame breaker mounts into Eaton Series C panelboards. It comes factory-equipped with line and load terminals accepting 4 AWG to 4/0 AWG wire. Rated 42kAIC at 600V, it utilizes fixed thermal-magnetic trip technology for dependable LI defense.
What does the L at the end of the HFDDC3200L catalog number indicate?
The L signifies that the circuit breaker is supplied from the factory with both line and load terminals included.
What is the standard replacement lug kit for this 200A breaker?
The standard terminal kit is Eaton part number 3TA225FD. These aluminum lugs accept 4 AWG to 4/0 AWG copper or aluminum conductors.
How must the breaker be wired to safely interrupt 600VDC?
To achieve the maximum 42kAIC rating at 600VDC, all three poles of the circuit breaker must be wired in series.
Can the HFDDC3200L be used in reverse-feed applications?
Yes. Because it utilizes a standard thermal-magnetic trip unit, this Series C F-frame breaker is suitable for reverse-feed installations.
Is this breaker rated for solar photovoltaic (PV) systems?
Yes. The HFDDC frame is part of Eaton's PVGard family. It is UL 489 Listed for DC applications, making it ideal for solar combiner boxes and battery storage systems.
Are the trip settings adjustable on the HFDDC3200L?
No. This breaker features fixed thermal and fixed magnetic trip elements. The overload and instantaneous short-circuit pickup levels cannot be adjusted in the field.
Can I field-install internal accessories like a shunt trip or auxiliary switch?
No. To maintain the factory seal and UL 489 listing on Eaton F-frame circuit breakers, all internal accessories must be factory-installed.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.