Eaton/Cutler-Hammer HKDDC3400A1301S5001Z01 3 Pole Circuit Breaker
The Eaton/Cutler-Hammer HKDDC3400A1301S5001Z01 is a 3 Pole thermal magnetic molded case circuit breaker with a current rating of 400 Amps and a voltage rating of 600V. It has an interrupting rating of 42kAIC at 600VDC. The HKDDC3400A1301S5001Z01 has a unit mounting type and includes long time and instantaneous trip functions.
Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Terminal Shields
Accessories
Auxiliary Switch (Factory Installed), Shunt Trip (Factory Installed), Lugs Not Included
Standards
CSA C22.2 No. 5, UL 489
Approval
CSA, UL
Temp Rating
40C
Construction Features
DC Rated, High Interrupting Capacity, PV Guard
Product FAQs
7 answers
Does the HKDDC3400A1301S5001Z01 come with standard terminal lugs?
No. The Z01 suffix in the catalog number indicates this breaker is supplied without standard line and load lugs. Installers must source the appropriate terminal hardware separately based on their specific wire size and application requirements.
What wire size does this breaker accept?
While the standard K-Frame lugs accept either two 3/0 AWG to 250 kcmil or one 3/0 AWG to 500 kcmil conductors, this specific Z01 variant is supplied without lugs. You must select and install terminal hardware that matches your required wire gauge and material.
How do the factory-installed accessories function on this breaker?
The built-in 48VDC shunt trip allows for remote opening of the breaker via an external control signal. The 2A/2B auxiliary switch provides two normally open and two normally closed contacts for remote status monitoring and signaling.
How should the poles be wired for DC applications?
For DC applications, multiple poles are typically connected in series to achieve the maximum voltage and interruption ratings. Always refer to Eaton installation instructions for the correct wiring configuration based on whether your system is grounded or ungrounded.
What do the A13 and S50 suffixes indicate on this breaker?
In the Eaton Series C nomenclature, the A13 suffix designates a factory-installed 2A/2B auxiliary switch. The S50 suffix indicates a factory-installed shunt trip, which is configured for 48VDC on this specific model.
How do I reset the breaker after a thermal trip?
In the event of a thermal overload trip, the thermal-magnetic trip unit must cool down before the circuit breaker can be reset. Always investigate and resolve the cause of the fault before reclosing the breaker.
How can I test the mechanical operation of this breaker?
You can use the push-to-trip button located on the front of the breaker to mechanically trip the unit. This checks the tripping function and should be used periodically to exercise the operating mechanism.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.