Delivering comprehensive LSIG protection, the Eaton LDC3600T106W is a 600A, 3-pole electronic molded case circuit breaker built for heavy-duty industrial applications. This unit-mount L-Frame breaker installs into Eaton Pow-R-Line 4 panelboards, switchboards, and motor control centers. Rated for a high interrupting capacity of 100 kAIC at 480VAC, it provides fully adjustable long-time, short-time, instantaneous, and ground fault settings.
Current Limiting, HACR Rated, High Interrupting Capacity, Optim 1050 Trip Unit, Ground Fault Protection, Trip-Free Mechanism, Visual Trip Indicator
Product FAQs
6 answers
What specific trip unit is included with the LDC3600T106W?
The T106 in the catalog number indicates it is equipped with a Digitrip OPTIM 1050 electronic trip unit. This allows you to fully adjust the Long-Time, Short-Time, Instantaneous, and Ground-Fault (LSIG) parameters for precise system coordination.
Which Eaton enclosures and panels accept the LDC3600T106W?
As a Series C L-frame breaker, it is designed to bolt directly into Eaton Pow-R-Line 4 panelboards, switchboards, and motor control centers.
Is there a difference between the Eaton and Cutler-Hammer versions of the LDC3600T106W?
No. Eaton acquired Cutler-Hammer, and the Series C L-frame breakers are identical whether they carry the Eaton or Cutler-Hammer label. They are exact drop-in replacements for one another.
Is the LDC3600T106W rated for 100% continuous operation?
No, standard Series C LDC breakers are rated for 80% continuous current. If your application requires a 100% continuous rating, you will need a breaker with the CLDC prefix.
How does the ground-fault protection work on the LDC3600T106W?
The integrated ground-fault function (the G in LSIG) is fully adjustable via the Digitrip OPTIM 1050 electronic trip unit. This allows you to set specific pickup and time-delay parameters to meet NEC requirements for 600A feeders and services.
Can the LDC3600T106W replace a standard LD-frame breaker?
Yes, the LDC3600T106W shares the same physical dimensions as standard LD breakers but offers a higher interrupting capacity, including 100kAIC at 480VAC. It can be used as a direct upgrade where higher fault current protection is required.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.