Skip to main content
Expedited shipping available at checkout

Eaton / Cutler-Hammer LGE3250FAG Molded Case Circuit Breaker

  • 250A
  • 3 Pole
  • Unit Mount
Eaton / Cutler-Hammer LGE3250FAG
Molded Case Circuit Breaker
Brand Eaton / Cutler-Hammer
SKU LGE3250FAG
Select Item Condition
Earn 3915 SuperPoints
  • 250A
  • 3 Pole
  • Unit Mount

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Eaton / Cutler-Hammer LGE3250FAG - 250A 3 Pole Molded Case Circuit Breaker

New

$3,915.00 In Stock

Quantity

Description

Built for commercial power distribution, this 250-amp LG-frame breaker utilizes high-speed blow-open action to limit peak current during fault conditions. The device installs into Eaton Series G panelboards, switchboards, and motor control centers without requiring specialized hardware. Equipped with fixed thermal and adjustable magnetic trip functions, it achieves a 65kAIC interrupt rating at 240VAC, ensuring robust performance for critical facility infrastructure and heavy machinery.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Part Number LGE3250FAG
Series LGE
Amperage 250A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 480VAC, 600VAC, 250VDC
Phase 3
AIC Rating 65kA @ 240VAC, 35kA @ 480VAC, 18kA @ 600VAC, 22kA @ 250VDC
Fit and installation
Frame Type LG
Terminal Type Lugs
For Use With Eaton Series G Panelboards, Switchboards, Motor Control Centers
Wire Gauge 3 AWG - 500 kcmil (Cu/Al)
Max Wire 500 kcmil
Min Wire 3 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Adjustable Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch
Accessories Line and Load Terminals
Standards CSA C22.2 No. 5, IEC 60947-2, NEMA AB 1, UL 489
Approval CE, CSA, IEC, UL
Temp Rating 40C
Construction Features HACR Rated, Current Limiting, High-Speed Blow-Open Action, 80% Rated

Product FAQs

8 answers
What type of wire and lugs are compatible with the LGE3250FAG?

This breaker includes standard line and load lugs that accept 3 AWG to 500 kcmil copper or aluminum conductors. Ensure proper torque specifications are applied during installation as indicated on the breaker faceplate.

Can the LGE3250FAG be used in reverse-feed applications?

Yes. Eaton Series G LG-frame thermal-magnetic circuit breakers are suitable for reverse-feed applications. They can be back-fed without issue since they do not contain electronic trip units with directional limitations.

What does the FAG suffix indicate in the LGE3250FAG catalog number?

The FA designates a fixed thermal and adjustable magnetic trip unit. The G indicates that standard line and load lug terminals are included from the factory.

Can I substitute an LGE325032W for the LGE3250FAG?

While both are 250A, 3-pole LG-frame breakers, they have different configurations. The LGE3250FAG uses a thermal-magnetic trip unit and includes lugs. The LGE325032W features an electronic LSI trip unit and comes without line or load terminals, which is indicated by the W suffix.

How should the LGE3250FAG be wired for 250VDC applications?

When applying this breaker on a 250VDC system, Eaton requires wiring two of the three poles in series to achieve the full 22kAIC interrupting rating.

Is the LGE3250FAG rated for 100 percent continuous load?

No. Because the catalog number does not include a 100 percent rating designator, this breaker carries a standard 80 percent continuous current rating. Continuous loads lasting three hours or more should not exceed 200 amps.

Does the LGE3250FAG provide ground fault protection?

No. This breaker is equipped with a standard thermal-magnetic trip unit providing Long-Time and Instantaneous (LI) protection. It does not include equipment ground fault protection (LSIG) or personnel ground fault circuit interruption (GFCI).

What equipment is the LGE3250FAG designed to mount in?

This unit-mount breaker is designed for installation in Eaton Series G panelboards, switchboards, and motor control centers. It mounts directly to the chassis or backpan using standard LG-frame hardware.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping