Built for commercial power distribution, this 250-amp LG-frame breaker utilizes high-speed blow-open action to limit peak current during fault conditions. The device installs into Eaton Series G panelboards, switchboards, and motor control centers without requiring specialized hardware. Equipped with fixed thermal and adjustable magnetic trip functions, it achieves a 65kAIC interrupt rating at 240VAC, ensuring robust performance for critical facility infrastructure and heavy machinery.
HACR Rated, Current Limiting, High-Speed Blow-Open Action, 80% Rated
Product FAQs
8 answers
What type of wire and lugs are compatible with the LGE3250FAG?
This breaker includes standard line and load lugs that accept 3 AWG to 500 kcmil copper or aluminum conductors. Ensure proper torque specifications are applied during installation as indicated on the breaker faceplate.
Can the LGE3250FAG be used in reverse-feed applications?
Yes. Eaton Series G LG-frame thermal-magnetic circuit breakers are suitable for reverse-feed applications. They can be back-fed without issue since they do not contain electronic trip units with directional limitations.
What does the FAG suffix indicate in the LGE3250FAG catalog number?
The FA designates a fixed thermal and adjustable magnetic trip unit. The G indicates that standard line and load lug terminals are included from the factory.
Can I substitute an LGE325032W for the LGE3250FAG?
While both are 250A, 3-pole LG-frame breakers, they have different configurations. The LGE3250FAG uses a thermal-magnetic trip unit and includes lugs. The LGE325032W features an electronic LSI trip unit and comes without line or load terminals, which is indicated by the W suffix.
How should the LGE3250FAG be wired for 250VDC applications?
When applying this breaker on a 250VDC system, Eaton requires wiring two of the three poles in series to achieve the full 22kAIC interrupting rating.
Is the LGE3250FAG rated for 100 percent continuous load?
No. Because the catalog number does not include a 100 percent rating designator, this breaker carries a standard 80 percent continuous current rating. Continuous loads lasting three hours or more should not exceed 200 amps.
Does the LGE3250FAG provide ground fault protection?
No. This breaker is equipped with a standard thermal-magnetic trip unit providing Long-Time and Instantaneous (LI) protection. It does not include equipment ground fault protection (LSIG) or personnel ground fault circuit interruption (GFCI).
What equipment is the LGE3250FAG designed to mount in?
This unit-mount breaker is designed for installation in Eaton Series G panelboards, switchboards, and motor control centers. It mounts directly to the chassis or backpan using standard LG-frame hardware.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.