Designed for custom configurations, the LGE340033W is a 3-pole, 400A MCCB from Eaton's Series G family. It is ideal for applications where specialized lug kits are required. This LG-frame MCCB is designed for unit mounting in Eaton panelboards and switchboards. Because it is supplied without standard terminals, installers can select exact connection hardware. The breaker features an electronic trip unit with adjustable LS protection and a 35 kAIC rating at 480VAC.
HACR Rated, Current Limiting, 80% Rated, True RMS Sensing
Product FAQs
8 answers
What enclosures are compatible with the Eaton LGE340033W circuit breaker?
This Series G LG-frame breaker is designed for installation in Eaton panelboards, switchboards, and motor control centers.
What protection functions are included in the LGE340033W trip unit?
It is equipped with a Digitrip 310+ electronic trip unit that provides adjustable Long-Time (L) and Short-Time (S) protection. It does not include ground fault protection.
How is the LGE340033W mounted inside an enclosure?
This is a unit-mount circuit breaker. It bolts directly to the mounting pan or chassis of the panelboard or switchboard rather than plugging into a busbar.
What does the 33 in the LGE340033W catalog number indicate?
The 33 suffix specifies that the breaker includes a Digitrip 310+ electronic trip unit configured for Long-Time and Short-Time (LS) trip functions.
Is the LGE340033W suitable for 480V commercial electrical systems?
Yes. It is rated for up to 600VAC. When installed in a 480VAC system, it carries a maximum interrupting rating of 35kAIC.
What is the maximum continuous current rating for the LGE340033W?
The breaker is rated for a maximum continuous current of 400 amps. Because it features an adjustable electronic trip unit, the long-time pickup can be dialed down to protect circuits with lower ampacity requirements.
Can I use the LGE340033W to replace an older Cutler-Hammer LG-frame breaker?
Yes. Eaton acquired Cutler-Hammer, and their Series G breakers are fully interchangeable. The LGE340033W will directly replace older Cutler-Hammer models bearing the exact same catalog number.
Does the LGE340033W provide ground fault equipment protection?
No. The LS trip function only covers Long-Time and Short-Time overcurrents. Applications requiring ground fault protection will need a breaker with an LSG or LSIG trip unit, such as the LGE340035W.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.