Engineered for commercial and industrial power distribution, this 600A molded case circuit breaker utilizes microprocessor-based sensing for accurate overcurrent protection. It installs into Eaton Series G panelboards, switchboards, and motor control centers using standard unit mounting. The adjustable long-time, short-time, and instantaneous (LSI) settings allow facility managers to fine-tune coordination, while the 35kAIC rating at 480VAC handles demanding fault conditions.
HACR Rated, Current Limiting, 80% Rated, True RMS Sensing
Product FAQs
9 answers
What does the 32G suffix in the LGE360032G catalog number indicate?
The 32 indicates the breaker is equipped with a Digitrip 310+ electronic trip unit featuring LSI (Long-Time, Short-Time, and Instantaneous) protection. The G signifies that standard line and load terminals are included.
What adjustments can be made on the Digitrip 310+ LSI trip unit?
The LSI electronic trip unit allows you to adjust the Long-Time pickup and delay, Short-Time pickup and delay, and Instantaneous pickup to coordinate with other protective devices in your electrical system.
Does the Digitrip 310+ trip unit have a test port?
Yes, the Digitrip 310+ includes a test port that allows you to perform a no-trip functional test using an Eaton test kit. The test LED also functions as a high load alarm indicator during normal operation.
What types of enclosures and equipment are compatible with the LGE360032G?
This LG-frame breaker is designed for use in Eaton Series G panelboards, switchboards, and motor control centers.
Does the LGE360032G come with mounting hardware and lugs?
Yes, the G suffix in the catalog number indicates that standard aluminum line and load lugs are factory-installed.
What is the recommended torque for the terminal mounting screws on the LG frame?
When securing the wire connecting terminals to the circuit breaker, Eaton recommends torquing the cap screws to 6 to 8 lb-ft.
Is it safe to install or perform maintenance on the LGE360032G while the panel is energized?
No. Always verify that no voltage is present before proceeding with installation or maintenance. Contact with energized equipment can result in severe personal injury or death.
Can the Series G LG-frame breaker directly replace an older Series C L-frame breaker?
While the Series G LG-frame covers similar amperage ranges as the legacy Series C L-frame, they have different physical dimensions and mounting footprints. Retrofit kits or panel modifications are typically required when replacing older L-frame units.
What is the maximum continuous current rating for the LG frame?
The LG frame has a maximum continuous current rating of 630 amps globally, but it is limited to 600 amps for UL and CSA listed applications.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.