The NGC308032E is an 800-amp, three-pole molded case circuit breaker from Eaton's Series G family. Engineered for commercial and industrial applications, it installs into compatible panelboards, switchboards, and motor control centers. This NG-frame breaker features an advanced electronic LSI trip unit, allowing for adjustable long-time, short-time, and instantaneous protection. Rated for 100 kAIC at 480VAC, it delivers high interrupting capacity and reliable reverse feed capabilities.
HACR Rated, Reverse Feed, 80% Rated, High Interrupting Capacity
Product FAQs
5 answers
What does the 32E in the catalog number indicate for this breaker?
The 32E suffix identifies the Digitrip 310+ electronic trip unit configuration. It signifies that the breaker has Long-Time, Short-Time, and Instantaneous (LSI) protection, but does not include ground fault protection. Systems requiring ground fault capabilities will need a different trip unit suffix, such as 35E for LSG or 36E for LSIG.
What is the difference between the NGC and NGH versions of this 800A breaker?
The third letter in the catalog number indicates the interrupting capacity tier. The NGC308032E is the very high interrupting tier, providing up to 100kAIC at 480VAC. The NGH version is the standard high tier, which provides 65kAIC at 480VAC. Both share the exact same NG-frame physical footprint.
Does the NGC308032E come with terminal lugs installed?
No. Eaton NG-frame circuit breakers do not ship with terminal lugs. This model features stud or tapped pad connections. You must purchase the appropriate Eaton lug kits separately or connect the breaker directly to busbars, depending on your switchboard or panelboard design.
What is the maximum continuous current the NGC308032E can handle?
Because this is a standard 80 percent rated breaker, continuous loads lasting three hours or more must be limited to 640 amps (80 percent of its nominal 800A rating). The full 800A capacity is only permitted for non-continuous loads. Eaton models that are 100 percent rated typically feature a C at the very end of the catalog number.
Can the NGC308032E be wired for bottom-feed configurations?
Yes. Eaton Series G NG-frame molded case circuit breakers are suitable for reverse feed applications. This allows panel builders to safely wire the line side to the bottom terminals if required by the enclosure layout.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.
Reviews
Review summary
Customers rate this product 5.0 out of 5 based on 1 review.