Delivering advanced circuit protection, the Eaton NGH312039E is a 1200A molded case circuit breaker. It features a Digitrip 310+ unit with ALSIG functions and ground fault monitoring. This 3-pole breaker utilizes a bolt-on mounting style for installation in Eaton Series G panelboards and switchboards. It replaces the PDG53M1200E5NN. Operating as a standard 80% rated device, it achieves 65kAIC at 480V. The built-in Arcflash Reduction Maintenance System ensures enhanced workplace safety.
CSA C22.2 No. 5, HACR, IEC 60947-2, NEMA AB 1, UL 489
Approval
CE, CSA, HACR, IEC, UL
Temp Rating
-20C to 70C
Construction Features
80% Rated, High Interrupting Capacity, HACR Rated, Reverse Feed, True RMS Sensing, Arcflash Reduction Maintenance System
Product FAQs
6 answers
What is the purpose of the ALSIG trip unit on the NGH312039E?
The ALSIG designation indicates this breaker features a Digitrip 310+ electronic trip unit with an Arcflash Reduction Maintenance System (ARMS), along with Long-Time, Short-Time, Instantaneous, and Ground-Fault protection. When activated during maintenance, ARMS reduces the fault clearing time, significantly lowering the available arc flash energy and improving personnel safety.
Which electrical distribution equipment is compatible with the NGH312039E?
This NG-frame breaker is designed for use in Eaton Series G panelboards, switchboards, and motor control centers. It is typically used for main and feeder protection in large three-phase commercial and industrial power distribution systems.
How are the line and load connections made on the NGH312039E?
This breaker features a bolt-on mounting style with stud and tapped pad terminals. It requires appropriate NG-frame mounting hardware and lugs to secure the conductors and ensure reliable electrical stability.
What is the Power Defense equivalent for the NGH312039E?
For modernization or replacement projects, the NGH312039E crosses over to the Eaton Power Defense PDG53M1200E5NN. Both are 1200A, 3-pole breakers that feature electronic trip units with an Arcflash Reduction Maintenance System.
Does the NGH312039E allow for selective coordination?
Yes, the Digitrip electronic trip unit is fully adjustable. Electricians can precisely tune the Long-Time, Short-Time, Instantaneous, and Ground-Fault (LSIG) settings to coordinate with downstream and upstream protective devices in the distribution system.
Is the NGH312039E rated for 80% or 100% continuous operation?
The NGH312039E is a standard 80% rated circuit breaker. Continuous loads should not exceed 80% of the 1200A nominal rating (960A) in accordance with standard National Electrical Code (NEC) sizing practices.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.