Eaton / Cutler-Hammer PDD23F0125TFFL - 125A 3 Pole Molded Case Circuit Breaker

Eaton / Cutler-Hammer PDD23F0125TFFL - 125A 3 Pole Molded Case Circuit Breaker

Re-Certified

$595.00 No Stock

Quantity

Description

Designed to handle higher current loads, this 125A three-phase molded case circuit breaker utilizes Eaton's Power Defense Frame 2 architecture. It provides essential fixed thermal and magnetic trip functions for commercial applications. The breaker installs into standard panelboards and offers a seamless transition from discontinued F-Frame EHD or FDB components via retrofit kits. Rated at 35kAIC, it includes load terminals and supports a wide range of field-installable accessories.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Series PDD
Amperage 125A
Poles 3
Mounting Style Panel Mount
Voltage 240VAC, 125VDC, 250VDC
Phase 3
AIC Rating 35kA @ 240VAC, 10kA @ 125VDC, 10kA @ 250VDC
Fit and installation
Frame Type PDG
Terminal Type Lugs
For Use With Eaton Power Defense Panelboards, Switchboards
Wire Gauge 4 AWG - 4/0 AWG (Al/Cu)
Max Wire 4/0 AWG
Min Wire 4 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Auxiliary Switch, Shunt Trip, Undervoltage Release, Alarm Switch, Padlock Attachment, Motor Operator, Rotary Handle
Accessories Load Terminals Only
Standards CSA, RoHS, UL 489
Approval CSA, UL
Temp Rating 40C
Construction Features HACR Rated, RoHS Compliant, Dual Rated (AC/DC)

Product FAQs

8 answers
What panelboards are compatible with the Eaton PDD23F0125TFFL?

This 3-pole breaker is designed for installation in Eaton Power Defense panelboards and switchboards.

What frame size does the PDD23F0125TFFL utilize?

It is built on the Eaton Power Defense Frame 2 architecture.

Is the trip unit on the PDD23F0125TFFL adjustable?

No, this model features a fixed thermal and fixed magnetic trip unit for long-time and instantaneous (LI) protection. The trip settings cannot be adjusted in the field.

What wire gauge is accepted by the terminals on this breaker?

The standard lugs accept either aluminum or copper wiring ranging from 4 AWG to 4/0 AWG.

Can the PDD23F0125TFFL be applied in direct current systems?

Yes, it is rated for DC applications with an interrupting capacity of 10 kAIC at both 125 VDC and 250 VDC.

Can this Power Defense breaker replace older Cutler-Hammer F-Frame models?

Yes, Frame 2 Power Defense breakers can serve as replacements for discontinued F-Frame components, such as EHD or FDB breakers, when installed with the correct retrofit kits.

How does the PDD23F0125TFFL connect to the panelboard?

It features a bolt-on connection type, meaning it must be mechanically fastened directly to the panelboard busbars rather than snapping into place.

Can the PDD23F0125TFFL be used on a 480V system?

No, this breaker has a maximum AC voltage rating of 240VAC. It is not safe or rated for use on 480V or 600V electrical systems.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.