Designed for critical industrial infrastructure, this 600A Power Defense Frame 3 breaker features a PXR20 LSIG electronic trip unit. It mounts into Eaton Pow-R-Line panelboards and replaces legacy LGH3600 or HLD3600 devices. The inclusion of ground fault protection alongside Modbus RTU connectivity provides engineers with superior diagnostic data, self-test functionality, and true RMS sensing for highly accurate power monitoring and system coordination.
What specific trip unit is installed in the PDG33M0600E3MJ?
This breaker is equipped with the Eaton PXR 20 electronic trip unit. The E3M designation in the catalog number specifies that it provides Long-Time, Short-Time, Instantaneous, and Ground Fault (LSIG) protection, and includes Modbus RTU communications and relays.
What type of lugs are included with this 600A Frame 3 breaker?
It includes standard line and load tunnel terminals, Eaton part number PDG3X3TA630. These aluminum lugs accept two conductors per phase, accommodating wire sizes from 2 AWG to 500 kcmil for both copper and aluminum wire.
Can the PDG33M0600E3MJ be applied on 240V or 600V systems?
Yes, it is globally rated for multiple voltage levels. While it has a 65kAIC interrupting rating at 480VAC, it is also fully rated to handle 100kAIC at 240VAC and 35kAIC at 600VAC.
Does this breaker include the Arcflash Reduction Maintenance System (ARMS)?
No, the E3M trip unit code indicates a standard PXR 20 LSIG unit without ARMS. If your application requires the Arcflash Reduction Maintenance System to lower incident energy levels, you will need to source a variant with the E5M trip unit code.
Which panelboards are designed to accept this breaker?
The PDG33M0600E3MJ is a Frame 3 Power Defense breaker designed for installation in Eaton Power Defense Frame 3 panelboards and Eaton Pow-R-Line panelboards.
Can I monitor the health and load status of this breaker remotely?
Yes, the integrated PXR 20 trip unit features Modbus RTU communications. This allows facility managers to monitor breaker health, load alarms, and ground fault alarms remotely using Eaton Power Xpert Protection Manager software.
Are the LSIG trip functions on this breaker adjustable?
Yes, the PXR 20 electronic trip unit provides adjustable settings for the Long-Time, Short-Time, Instantaneous, and Ground Fault protection bands, allowing for precise coordination with your electrical system requirements.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.