Skip to main content

Eaton / Cutler-Hammer PDG53K1200E2NN Molded Case Circuit Breaker

  • 1200A
  • 3 Pole
  • Unit Mount
Eaton / Cutler-Hammer PDG53K1200E2NN
Molded Case Circuit Breaker
Brand Eaton / Cutler-Hammer
SKU PDG53K1200E2NN
Select Item Condition
Earn 10037 SuperPoints
  • 1200A
  • 3 Pole
  • Unit Mount

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Eaton / Cutler-Hammer PDG53K1200E2NN - 1200A 3 Pole Molded Case Circuit Breaker

New

$10,037.02 Check Stock

Quantity

Description

Built for demanding industrial environments, the PDG53K1200E2NN is a 3-pole, 1200A molded case circuit breaker from the Power Defense Frame 5 family. It replaces older ND31200T52W models, offering upgraded microprocessor-based protection for modern electrical systems. Designed for unit mounting, it fits seamlessly into Eaton Pow-R-Line panelboards and enclosures. The breaker delivers 50 kAIC at 480V and includes a PXR20 LSI electronic trip unit with imperial hardware.

Specifications

Key specifications
Brand Eaton / Cutler-Hammer
Series PDG5
Amperage 1200A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 480Y/277VAC, 480VAC, 600Y/347VAC, 600VAC
Phase 3
AIC Rating 85kA @ 240VAC, 50kA @ 480Y/277VAC, 50kA @ 480VAC, 25kA @ 600Y/347VAC, 25kA @ 600VAC
Electrical ratings
Amperage Range 480-1200A
Fit and installation
Frame Type Complete Breaker
Terminal Type Lugs
For Use With Eaton Power Defense Enclosures, Switchboards, Pow-R-Line Panelboards
Max Wire 4/0 AWG
Min Wire 500 AWG
Protection and operation
Trip Technology Electronic Trip
Trip Function Code LSI
Trip Function Long-Time, Short-Time, Instantaneous
Trip Adjustability Adjustable
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Padlock Attachment, Rotary Handle, Communication Module
Accessories Modbus RTU Communication Module, Relays
Standards CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval CCC, CE, CSA, IEC, UL, UL 489
Temp Rating -20C to 70C
Construction Features True RMS Sensing, Self-Test, RoHS Compliant

Product FAQs

5 answers
What legacy Cutler-Hammer circuit breaker does the PDG53K1200E2NN replace?

This Power Defense Frame 5 breaker serves as the modern, upgraded replacement for the legacy ND31200T52W molded case circuit breaker.

Can I install this breaker in an older Pow-R-Line panelboard?

Yes, the PDG53K1200E2NN is designed for unit mounting and is fully compatible with Eaton Pow-R-Line panelboards, as well as standard switchboards and Power Defense enclosures.

What is the acceptable wire size range for the terminals on this 1200A breaker?

The factory-installed lugs are designed to accept conductors ranging from 4/0 AWG to 500 kcmil. Because this is a 1200A frame, multiple conductors per phase are required to meet ampacity codes.

How does the electronic trip unit handle harmonic distortion in industrial environments?

The integrated PXR 20 LSI electronic trip unit utilizes true RMS sensing. This ensures accurate current measurement and reliable overcurrent protection even when non-linear loads introduce harmonic distortion into the system.

Does this breaker support remote monitoring and testing?

Yes, the PXR 20 electronic trip unit features a micro-B USB port for use with Eaton's Power Xpert Protection Manager (PXPM) software. This allows technicians to safely test, configure, and troubleshoot the breaker.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.