Skip to main content
Expedited shipping available at checkout

Eaton / Westinghouse GC3100 Molded Case Circuit Breaker

  • 100A
  • 3 Pole
  • Unit Mount
Eaton / Westinghouse GC3100
Molded Case Circuit Breaker
Brand Eaton / Westinghouse
SKU GC3100
Select Item Condition
Earn 225 SuperPoints
  • 100A
  • 3 Pole
  • Unit Mount

Quantity

Bulk Pricing
Send your parts list for a volume quote.

Eaton / Westinghouse GC3100 - 100A 3 Pole Molded Case Circuit Breaker

Re-Certified

$225.71 In Stock

Quantity

Description

Part of the Series C family, this Eaton 100A molded case circuit breaker provides robust commercial and industrial power distribution. It features a compact G-frame design suited for motor control centers. Designed as an exact replacement, it mounts into legacy Westinghouse and Cutler-Hammer Series C panelboards without adapters. This unit serves as a direct substitute for the GD3100. Rated for 65kAIC at 240VAC, it utilizes fixed thermal-magnetic trip units for dependable LI protection.

Specifications

Key specifications
Brand Eaton / Westinghouse
Series GC
Amperage 100A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 125/250VDC
Phase 3
AIC Rating 65kA @ 240VAC, 10kA @ 125/250VDC
Fit and installation
Frame Type GC
Terminal Type Lugs
For Use With Eaton Series C Panelboards, Westinghouse Series C Panelboards, Motor Control Centers
Wire Gauge 14-1/0 AWG
Max Wire 1/0 AWG
Min Wire 14 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Fixed Thermal, Fixed Magnetic
Standards and features
Available Options Shunt Trip, Auxiliary Switch, Undervoltage Release, Alarm Switch, Padlock Attachment, DIN Rail Adapter, Base Mounting Plate
Accessories Line and Load Lugs Included
Standards CSA C22.2 No. 5.1, IEC 157-1, NEMA AB 1, UL 489
Approval CSA, UL
Temp Rating 40C
Construction Features HACR Rated, High Interrupting Capacity, Non-Interchangeable Trip

Product FAQs

9 answers
Which panelboards are compatible with the GC3100 circuit breaker?

This Series C G-frame breaker is designed for use in Eaton and Westinghouse Series C panelboards, as well as compatible motor control centers (MCCs).

Does the GC3100 bolt directly onto a panelboard bus?

No, the GC3100 is a unit-mount, feed-thru breaker designed for cable-in/cable-out connections. It is typically installed using a base mounting plate or DIN rail hardware rather than bolting to a busbar.

Are the line and load lugs included with this breaker?

Yes, the GC3100 comes equipped with standard line and load lugs that accept 14 to 1/0 AWG conductors.

Are the trip settings adjustable on the GC3100?

No, this breaker utilizes a fixed thermal and fixed magnetic trip unit. It provides standard long-time and instantaneous (LI) protection that cannot be field-adjusted.

Can I substitute a GC3100 for a GHC3100?

It depends on your system voltage. The GC3100 is rated for a maximum of 240VAC, while the GHC3100 is rated for up to 480Y/277VAC. Do not use the GC3100 if your system voltage exceeds 240VAC.

How do I reset the breaker after an overcurrent trip?

When tripped, the handle moves to a center position and exposes a white indicator strip. You must push the handle firmly to the extreme OFF position to reset the internal mechanism before switching it back to ON.

Is the GC3100 suitable for direct current (DC) circuits?

Yes, in addition to its AC ratings, this breaker is rated for 125/250VDC systems, providing up to 10kA of interrupting capacity for DC applications.

Where are the lug torque requirements listed for the GC3100?

The specific torque values for the line and load terminals are printed directly on the front nameplate of the breaker. Always use a calibrated torque wrench to ensure proper termination.

Can I field-install internal accessories like a shunt trip in the GC3100?

No, GC-frame breakers are factory-sealed. To maintain the UL489 listing, internal accessories such as shunt trips, auxiliary switches, or undervoltage releases must be installed at the factory.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.