Mounting into classic Westinghouse switchboards, the HLM3800 is an 800A, 3-pole MCCB from Eaton's Series C L-Frame lineup. It provides reliable thermal-magnetic protection with an adjustable magnetic trip. Designed to fit Pow-R-Line panelboards and motor control centers, it ensures a seamless installation. It serves as an exact replacement for discontinued systems, superseded by the HMDL3800 for newer setups. Rated at 35kAIC at 480V, it features Mark 75 high interrupting capacity.
High Interrupting Capacity, Interchangeable Trip Unit
Product FAQs
5 answers
Will an Eaton HLM3800 fit in my older Westinghouse motor control center or switchboard?
Yes. Eaton acquired the Westinghouse distribution equipment line, and the modern Eaton or Cutler-Hammer HLM3800 is the exact same Series C LM-frame breaker as the original. It will physically fit and integrate into vintage Westinghouse MCCs, switchboards, and Pow-R-Line panelboards without modification.
What does the H in the HLM3800 catalog number indicate?
The H designates this as the high-interrupting capacity version of the standard LM frame. It provides a 35kA interrupting rating at 480VAC, compared to the 18kA rating of a standard LM3800 breaker.
What is the modern replacement for the HLM3800 circuit breaker?
The HLM3800 is a legacy Series C breaker. For newer setups or when migrating to current standards, the Eaton HMDL3800 is the direct superseding replacement. However, the HLM3800 remains an exact fit for vintage Westinghouse enclosures without requiring complex retrofits.
How does the LI trip unit on the HLM3800 function?
The LI designation stands for Long-Time and Instantaneous protection. The Long-Time thermal element is fixed at 800 amps for continuous overload protection. The Instantaneous magnetic trip is adjustable, allowing electricians to fine-tune the short-circuit response to coordinate with downstream devices.
What size wire do the standard lugs on the HLM3800 accept?
When equipped with standard lugs, the HLM3800 accepts three 3/0 AWG to 400 kcmil aluminum or copper conductors per phase. Always use a calibrated torque wrench to meet the manufacturer specifications during installation.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.