Maintaining older electrical distribution systems requires exact-fit components like the Eaton QNP3050. This 50-amp, three-pole plug-on breaker provides essential thermal-magnetic protection with a 10kAIC interrupt rating at 240VAC, making it ideal for commercial facilities. It installs into legacy Westinghouse, Quicklag, and Eaton Pow-R-Line panels without modification. For users seeking current-generation equivalents, this legacy model is officially replaced by the QP3050 substitute.
This breaker is designed for use in legacy Westinghouse, Quicklag, and Eaton Pow-R-Line panelboards that accept plug-on Quicklag breakers.
Can I install this breaker in a residential Eaton BR or CH load center?
No. The QNP series is specifically designed for commercial Pow-R-Line and legacy Westinghouse panelboards. It will not fit standard residential BR or CH load centers.
How does this breaker mount into the panel?
The QNP3050 features a plug-on mounting style. It snaps directly onto the busbar of compatible Quicklag or Pow-R-Line panelboards, unlike the BAB series which requires bolted connections.
What wire sizes are accepted by the terminals on this 50A breaker?
The box lugs are designed to accept conductors ranging from 14 AWG to 4 AWG. Always verify the correct torque specifications based on the wire size and material used.
What does the LI trip function mean for this model?
The LI designation indicates a thermal-magnetic trip unit providing Long-Time (thermal overload) and Instantaneous (magnetic short-circuit) protection. Both trip settings are fixed and non-adjustable.
Can this 50A breaker be used on a 480V system?
No. The maximum voltage rating for this component is 240V AC. It is not rated for use on 480V or 277V electrical systems.
Is this breaker still manufactured under the Westinghouse brand?
Westinghouse electrical distribution equipment was acquired by Eaton. Depending on the production year, this exact component may be branded as Eaton, Cutler-Hammer, or Westinghouse.
What is the current-generation replacement for the QNP3050?
For users seeking a current-generation equivalent, this legacy model is officially replaced by the Eaton QP3050 circuit breaker.
What is the maximum continuous load permitted for this 50A breaker?
Standard molded case circuit breakers are rated for 80 percent continuous load unless marked otherwise. For this 50A breaker, the maximum continuous load should not exceed 40 amps.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.