Rated 22 kAIC at 120/240V, this 20A molded case circuit breaker delivers essential 5mA ground-fault and thermal-magnetic overcurrent protection. The GE THHQB2120GFT is built to handle demanding residential, commercial, and industrial loads. Featuring a bolt-on mounting style, it integrates seamlessly into GE A-Series and ReliaGear RQ panelboards. This unit replaces the older THHQB2120GF. Equipped with self-test capabilities and an internal common trip, it ensures code-compliant safety.
HACR Rated, Common Trip, Quick-Make/Quick-Break, Trip-Free Mechanism, Visual Trip Indicator, Non-Interchangeable Trip, Self-Test, Class A GFCI
Product FAQs
6 answers
Can I use the THHQB2120GFT to replace a THQB2120GFT?
Yes. The THHQB2120GFT has a higher interrupting rating of 22kAIC compared to the standard THQB2120GFT, which is rated at 10kAIC. They share the same physical dimensions and bolt-on mounting, making the THHQB a direct, upgraded replacement where higher fault current protection is required.
Will this breaker fit in a standard GE residential load center?
No. The THHQB2120GFT is a bolt-on circuit breaker designed specifically for commercial GE A-Series and ReliaGear RQ panelboards. Standard GE residential load centers require plug-in style breakers, such as the THQL series.
What level of ground fault protection does the THHQB2120GFT provide?
It provides Class A personnel-level ground fault protection, which trips at a 5mA leakage threshold. The GFT suffix also indicates that the breaker includes an automatic self-test feature to continuously verify the integrity of the ground fault circuitry.
How is the neutral wired on this GFCI breaker?
This breaker is equipped with a pigtail neutral wire that must be connected directly to the panelboard neutral bus. Additionally, the load neutral conductor must be terminated directly on the breaker to ensure proper ground fault sensing.
Is there a difference between ABB and GE branded THHQB2120GFT breakers?
No. Following ABB's acquisition of GE Industrial Solutions, these breakers may be labeled under either the ABB or General Electric brand. The form, fit, function, and internal components remain identical regardless of the logo on the label.
What does the LIG trip function indicate on this breaker?
LIG stands for Long-Time, Instantaneous, and Ground-Fault. The Long-Time function provides thermal protection against overloads, the Instantaneous function provides magnetic protection against short circuits, and the Ground-Fault function protects personnel from earth leakage currents.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.