Engineered for continuous duty, the ABB T2SQ050TL is a 3-pole, 50A molded case circuit breaker from the legacy SACE Tmax T2 series. This unit is 100% rated, allowing it to carry its full 50A capacity continuously without standard derating. It mounts into ABB Tmax T2 enclosures and switchboards. It is replaced by the XT1SU3050AFF000XXX, though the replacement is standard 80% rated and requires an adapter.
Shunt Trip, Auxiliary Switch, Undervoltage Release, Bell Alarm, DIN Rail Adapter, Motor Operator, Rotary Handle
Accessories
Lugs
Standards
CSA C22.2 No. 5.1, IEC 60947-2, UL 489
Approval
CE, CSA, IEC, UL
Temp Rating
40C
Construction Features
100% Rated, HACR Rated, Reverse Feed
Product FAQs
7 answers
What is the direct replacement for the legacy T2SQ050TL breaker?
ABB replaces this legacy SACE Tmax T2 breaker with the XT1SU3050AFF000XXX. However, the XT1 replacement is standard 80 percent rated and requires a retrofit adapter to fit into existing T2 spaces.
Does the T2SQ050TL require standard continuous current derating?
No. Unlike standard breakers that must be derated to 80 percent for continuous loads, the T2SQ050TL is 100 percent rated. It can carry its full 50-amp load continuously.
Can I install the T2SQ050TL on a standard DIN rail?
Out of the box, the T2SQ050TL is a unit mount breaker designed for ABB Tmax T2 enclosures and switchboards. Mounting it on a DIN rail requires a separate DIN rail adapter accessory.
Are the terminals on the T2SQ050TL suitable for aluminum wiring?
Yes, the standard lugs included with this breaker are dual-rated for both copper and aluminum conductors ranging from 14 AWG to 1/0 AWG. Ensure you apply the correct torque and use an appropriate oxide inhibitor when terminating aluminum wire.
Can I adjust the trip settings on the T2SQ050TL?
No, this breaker features a fixed thermal-magnetic trip unit. Both the long-time thermal and instantaneous magnetic trip functions are factory set and cannot be adjusted in the field.
Can this breaker be reverse fed?
Yes, the T2SQ050TL is suitable for reverse feed applications. This allows flexibility in wiring the line and load connections depending on your panel layout.
Is the T2SQ050TL suitable for use with HVAC equipment?
Yes, this breaker is HACR rated, meaning it is certified for use with heating, air conditioning, and refrigeration equipment motor loads.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.