Rated at 150kAIC at 240V, the ABB XT2HU3125FYD000XXX is a 3-pole, 125A molded case circuit breaker from the SACE Tmax XT2 line. It is engineered to handle demanding commercial and industrial electrical loads safely. Designed for unit mounting, it integrates seamlessly into ReliaGear neXT panelboards and SB switchboards. It also replaces discontinued GE Spectra SELA36AT0125 and ABB Tmax T3H125TW breakers.
ABB ReliaGear neXT Panelboards, ReliaGear SB Switchboards
Wire Gauge
10-2/0 AWG
Max Wire
2/0 AWG
Min Wire
10 AWG
Protection and operation
Trip Technology
Electronic Trip
Trip Function Code
LSI
Trip Function
Long-Time, Short-Time, Instantaneous
Trip Adjustability
Adjustable
Standards and features
Available Options
Shunt Trip, Auxiliary Switch, Undervoltage Release, Motor Operator, Padlock Attachment, Terminal Lugs, DIN Rail Adapter
Accessories
Lugs Not Included
Standards
CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval
CE, CSA, cULus, IEC, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Current Limiting, Double Insulated, Reverse Feed
Product FAQs
5 answers
Which panelboards and switchboards are compatible with the XT2HU3125FYD000XXX?
This breaker is designed for integration into ABB ReliaGear neXT Panelboards and ReliaGear SB Switchboards. It is commonly used in commercial and industrial power distribution systems.
What does the LSI trip function provide on this electronic trip breaker?
The LSI electronic trip unit allows you to adjust the Long-Time (overload), Short-Time (short circuit with intentional delay), and Instantaneous (immediate short circuit) protection settings. This adjustability is critical for proper selective coordination with downstream and upstream breakers in your facility.
What wire sizes do the factory lugs accept?
The included lugs accommodate wire gauges ranging from 10 AWG to 2/0 AWG. Always verify your conductor material and temperature ratings against local electrical codes during installation.
Can this ABB Tmax XT breaker be used in DC applications?
Yes, it is rated for direct current systems up to 500VDC, where it provides a 65kA interrupting capacity.
How is this circuit breaker mounted inside an enclosure?
This is a unit mount breaker. It is designed to be bolted directly to a backpan or mounting plate rather than plugging into a standardized busbar.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.