Designed for commercial and industrial power distribution, the XT2NU3125BFF000XXX is a 3-pole, 125A molded case circuit breaker from the SACE Tmax XT2 series. It provides reliable overcurrent protection. This unit mount MCCB installs into ABB ReliaGear neXT panelboards and ReliaGear SB switchboards. It serves as a replacement for legacy GE Spectra SEHA36AT0125 and ABB Tmax T3N125TW breakers. Rated for 65kA at 240VAC, it features a current-limiting, double-insulated design.
ABB ReliaGear neXT Panelboards, ReliaGear SB Switchboards
Wire Gauge
10-2/0 AWG
Max Wire
2/0 AWG
Min Wire
10 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Adjustable Thermal, Adjustable Magnetic
Standards and features
Available Options
Shunt Trip, Auxiliary Switch, Undervoltage Release, Motor Operator, Padlock Attachment, Terminal Lugs, DIN Rail Adapter
Accessories
Lugs Not Included
Standards
CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval
CE, CSA, cULus, IEC, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Double Insulated, Reverse Feed
Product FAQs
5 answers
What panelboards are compatible with the XT2NU3125BFF000XXX?
This breaker is designed for use with ABB ReliaGear neXT panelboards and ReliaGear SB switchboards. It utilizes a bolt-on connection for secure installation in these systems.
Can the Tmax XT2 series replace legacy GE Spectra RMS breakers?
Yes, the ABB SACE Tmax XT series is the direct replacement for the retired GE Spectra RMS line. ABB offers specific retrofit kits that allow you to install Tmax XT breakers into existing GE Spectra panelboards and switchboards.
How does the adjustable thermal-magnetic trip unit work on this breaker?
This breaker features an adjustable thermal and adjustable magnetic trip unit. The long-time thermal setting allows you to fine-tune overload protection, while the instantaneous magnetic setting lets you adjust the short-circuit response threshold to coordinate with downstream devices.
What wire sizes are accepted by the lugs on this XT2 breaker?
The factory-installed lugs accept wire gauges ranging from 10 AWG to 2/0 AWG. Ensure proper torque specifications are followed during installation as outlined in the ABB Tmax XT instruction manual.
Can this breaker be used in DC applications?
Yes, this breaker is rated for up to 500VDC with an interrupting capacity of 35kAIC. When wiring for DC systems, verify the required pole series connections per ABB guidelines to safely interrupt the DC fault current.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.