ABB XT4LU3100BFJ000XXX Molded Case Circuit Breaker

  • 100A
  • 3 Pole
  • Unit Mount
ABB XT4LU3100BFJ000XXX
Molded Case Circuit Breaker
Brand ABB
SKU XT4LU3100BFJ000XXX
Select Item Condition
Earn 2027 SuperPoints
  • 100A
  • 3 Pole
  • Unit Mount

Quantity

Bulk Pricing
Send your parts list for a volume quote.

ABB XT4LU3100BFJ000XXX - 100A 3 Pole Molded Case Circuit Breaker

New

$2,027.10 In Stock

Quantity

Description

Part of the SACE Tmax XT family, this 3-pole 100A molded case circuit breaker provides reliable LI protection for commercial and industrial systems. The unit features a TMA adjustable thermal and magnetic trip unit, allowing precise coordination within your electrical distribution network. Designed for unit mounting, it installs into ABB ReliaGear neXT panelboards and switchboards.

Specifications

Key specifications
Brand ABB
Series XT4
Amperage 100A
Poles 3
Mounting Style Unit Mount
Voltage 240VAC, 480VAC, 600VAC, 250VDC, 600VDC
Phase 3
AIC Rating 200kA @ 240VAC, 100kA @ 480VAC, 50kA @ 600VAC, 85kA @ 250VDC, 75kA @ 600VDC
Electrical ratings
Amperage Range 70-100A
Fit and installation
Frame Type XT4L
Terminal Type Lugs
For Use With ABB ReliaGear neXT Panelboards, Switchboards
Wire Gauge 4 AWG - 300 kcmil (Cu/Al)
Max Wire 300 kcmil
Min Wire 4 AWG
Protection and operation
Trip Technology Thermal Magnetic
Trip Function Code LI
Trip Function Long-Time, Instantaneous
Trip Adjustability Adjustable Thermal, Adjustable Magnetic
Standards and features
Available Options Auxiliary Switch, Shunt Trip, Undervoltage Release, Lug Kits, Motor Operator, Rotary Handle
Accessories Front Terminals Included, Lugs Not Included
Standards CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval CCC, CSA, cULus, IEC, KEMA, RINA, UL
Temp Rating -25C to 70C
Construction Features Current Limiting, Reverse Feed, 100% Rated, Double Insulation

Product FAQs

6 answers
What equipment is this XT4L breaker designed to fit?

This unit mount breaker is engineered for installation in ABB ReliaGear neXT panelboards and ReliaGear SB switchboards.

What does the "L" in the XT4L frame designation stand for?

The "L" indicates an Extra High interrupting capacity tier within the ABB SACE Tmax XT family, delivering a 100kA rating at 480VAC for demanding industrial applications.

How is the trip unit configured on this breaker?

It utilizes a thermal magnetic trip unit with both adjustable thermal and adjustable magnetic settings, allowing electricians to precisely coordinate long-time and instantaneous fault protection.

What are the wiring requirements for the standard lugs?

The front lug terminals are rated for both copper and aluminum conductors, accepting wire sizes from 4 AWG up to 300 kcmil.

Can this breaker be used in direct current (DC) systems?

Yes, it is fully rated for DC applications, providing up to 85kA of interrupting capacity at 250VDC and 75kA at 600VDC.

Is the ABB XT4LU3100BFJ000XXX a current-limiting breaker?

Yes, the XT4L frame features current-limiting technology, which rapidly clears short circuits to reduce let-through energy and protect sensitive downstream equipment.

SuperClub

Join free. Get 500 SuperPoints.

Earn points on eligible purchases and redeem them at checkout.

100 SuperPoints = $1 off.

Warranties

60-Day Warranty

Your purchase includes 60 days of SuperBreakers warranty coverage.

Get a Quote

Don’t see what you’re looking for?

We source obsolete and hard-to-find parts every day.

Shipping

Free Shipping Policy

Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.

Read our full shipping policy

Same Day Shipping

We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.

Expedited Shipments

Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.

International Shipping

All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.