Offering adjustable thermal and magnetic trip settings, this 150-amp breaker allows precise LI protection tuning for complex industrial loads. It integrates into ABB ReliaGear neXT power panels, ReliaGear SB switchboards, and standard XT panelboards. This unit replaces older T4N150TW models, bringing modern current-limiting capabilities to existing infrastructure. It features front terminals for versatile connection options and carries a robust 65kA interrupt rating at 240VAC.
Which panelboards and switchboards are compatible with this 150A XT4 breaker?
This breaker is designed for use with ABB ReliaGear neXT Power Panels, ReliaGear SB Switchboards, and SACE Tmax XT Panelboards.
How does the thermal magnetic trip unit function on this XT4 breaker?
It features an LI (Long-Time, Instantaneous) trip function. The adjustable thermal setting protects against overloads, while the adjustable magnetic setting provides short-circuit protection.
What wire sizes are accepted by the standard lugs on this breaker?
The standard lugs accept 4 AWG to 300 kcmil copper (Cu) or aluminum (Al) conductors.
Can this XT4 breaker replace older legacy GE breakers?
Yes, the SACE Tmax XT4 series is the modern replacement for legacy GE T4N150TW models, upgrading existing infrastructure with current-limiting capabilities.
How is the breaker secured into a ReliaGear neXT panelboard?
It utilizes a plug-in rail system where the breaker is pushed into the bus stack and secured with mounting screws. The grooves on the breaker insulator must align with the bus stack cover to ensure full insertion.
What is the reference ambient temperature for the thermal magnetic trip unit?
The reference temperature for the trip unit calibration is +40 degrees Celsius. Operating outside this temperature may require consulting performance derating tables.
Can this 3-pole XT4 breaker be used in single-phase applications?
Yes, XT4 three-pole circuit breakers equipped with thermal magnetic trip units are suitable for single-phase applications up to 600VAC according to UL standards.
Does this breaker support field-installable internal accessories?
Yes, the SACE Tmax XT4 frame supports common internal accessories like auxiliary contacts, shunt trips, and undervoltage releases, which can be installed in the field.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.