Engineered for heavy-duty power distribution, the ABB XT5HU360BBYN000XXX is a 3-pole, 600A molded case circuit breaker from the SACE Tmax XT family. It provides reliable overcurrent protection with a robust 65kAIC rating at 480VAC. This unit mount MCCB installs into ReliaGear neXT panelboards, switchboards, and motor control centers. It serves as a drop-in replacement for legacy T5H600BW breakers. Featuring an adjustable thermal magnetic trip unit (LI), it includes line and load side lugs.
ReliaGear neXT Panelboards, Switchboards, Motor Control Centers
Wire Gauge
2x 2/0 AWG - 500 kcmil (Cu/Al)
Max Wire
500 kcmil
Min Wire
2/0 AWG
Protection and operation
Trip Technology
Thermal Magnetic
Trip Function Code
LI
Trip Function
Long-Time, Instantaneous
Trip Adjustability
Adjustable Thermal, Adjustable Magnetic
Standards and features
Available Options
Auxiliary Switch, Shunt Trip, Undervoltage Release, Motor Operator, Handle Lock
Accessories
Line Side Panel Connectors, Load Side Lugs Included
Standards
CSA C22.2 No. 5, IEC 60947-2, UL 489
Approval
CCC, CSA, cULus, IEC, UL
Temp Rating
-25C to 70C
Construction Features
HACR Rated, Current Limiting, Reverse Feed
Product FAQs
7 answers
Does the XT5HU360BBYN000XXX replace older GE circuit breakers?
Yes. Following ABB's acquisition of GE Industrial Solutions, the Tmax XT5 series is the direct replacement for legacy GE Spectra RMS SG600 frame circuit breakers. Retrofit kits are available to install this breaker into existing Spectra panelboards and switchboards.
What equipment is the XT5HU360BBYN000XXX designed to be installed in?
This unit mount molded case circuit breaker is designed for use in ABB and GE ReliaGear neXT panelboards, switchboards, and motor control centers.
What does the H in the XT5H frame designation indicate?
The H indicates a High interrupting capacity. For this specific 600A breaker, it provides an interrupting rating of 65kAIC at 480VAC and 35kAIC at 600VAC.
How does the thermal magnetic trip unit on this breaker operate?
The XT5HU360BBYN000XXX features a TMA (Thermal Magnetic Adjustable) trip unit with LI functions. This allows you to adjust both the long time (thermal) settings for overload protection and the instantaneous (magnetic) settings for short circuit protection to coordinate with your specific system requirements.
Can the XT5HU360BBYN000XXX be used in DC electrical systems?
Yes, this breaker is rated for both AC and DC applications. It supports up to 600VDC, providing a 70kAIC interrupting rating at 250VDC, 50kAIC at 500VDC, and 35kAIC at 600VDC.
What are the wire size requirements for the lugs on this 600A breaker?
The included lugs accept two conductors per phase, accommodating wire sizes from 2/0 AWG up to 500 kcmil. The terminals are rated for both copper and aluminum conductors.
What maintenance is required for the thermal magnetic trip unit?
Standard maintenance includes periodically exercising the breaker by manually toggling it on and off to keep the mechanical linkages free of dust and debris. You should also verify that the adjustable thermal and magnetic dials remain set to the values specified by your coordination study.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.