Engineered for heavy-duty industrial applications, the ABB XT5LU360BFYN000XXX delivers reliable 600A power distribution. This three-pole molded case circuit breaker is part of the SACE Tmax XT family. It installs into ReliaGear neXT panelboards, SB switchboards, and standard XT enclosures, serving as a reliable upgrade for legacy Spectra RMS SG600 frames.
HACR Rated, Current Limiting, Reverse Feed, True RMS Sensing
Product FAQs
8 answers
Which panelboards and switchboards are compatible with the XT5LU360BFYN000XXX?
This unit mount breaker is designed for use in ABB ReliaGear neXT panelboards, ReliaGear SB switchboards, and ABB SACE Tmax XT enclosures.
How does the LSI electronic trip unit function on this 600A breaker?
The LSI designation indicates adjustable settings for Long-Time, Short-Time, and Instantaneous trip functions. This allows electricians to precisely shape the time-current curve for optimal selective coordination with downstream devices.
What does the L in the XT5L frame designation indicate?
In the ABB SACE Tmax XT series, the L denotes the interrupting capacity tier. For the XT5 frame, it specifies an extra high interrupting rating of 100kA at 480VAC and 200kA at 240VAC.
How are the conductors terminated on the XT5LU360BFYN000XXX?
The breaker is equipped with standard lugs that accept two conductors per phase. The acceptable wire range is 2/0 AWG to 500 kcmil. Always verify proper torque values in the ABB installation instructions before energizing.
Can the XT5LU360BFYN000XXX be used to replace legacy GE Spectra breakers?
Yes, the ABB SACE Tmax XT5 series is the direct replacement path for discontinued GE Spectra RMS SG600 frame breakers. When upgrading existing panels, specific retrofit kits may be required depending on the enclosure.
How is the XT5LU360BFYN000XXX mounted within a panel?
This is a unit mount breaker, meaning it is bolted directly to the chassis or buswork rather than snapping into place. It is compatible with ReliaGear neXT and SB switchboard mounting hardware.
Does this XT5 breaker support DC voltage systems?
Yes, the XT5LU360BFYN000XXX is rated for use in DC systems up to 600VDC, where it provides an interrupting capacity of 50kA.
Can this breaker be installed in a standalone enclosure?
Yes, the XT5LU360BFYN000XXX is compatible with ABB SACE Tmax XT enclosures for applications requiring a standalone enclosed circuit breaker.
SuperClub
Join free. Get 500 SuperPoints.
Earn points on eligible purchases and redeem them at checkout.
We source obsolete and hard-to-find parts every day.
Shipping
Free Shipping Policy
Parcel shipments with item value over $99 qualify for free economy shipping within the continental US. Please call to confirm special handling instructions. We do not charge a handling fee or require a minimum amount on any order. SuperBreakers does not ship on customer accounts.
We strive to ship out your items the same day the order is placed. In rare circumstances SuperBreakers may reserve up to 5 business days to consolidate orders for complete shipment.
Expedited Shipments
Orders being shipped via Next Day Air, 2 Day Shipping or 3 Day Shipping must be received by 3 PM EST to guarantee same-day shipments. Expedited orders only ship on normal business days. Shipments will NOT be sent out on Saturdays and Sundays.
International Shipping
All International orders require a $1,000 minimum order threshold. Due to the special nature of these shipments, we require that these be placed with a SuperBreakers representative. Additional shipping and instructions will apply. All International Orders are Non-Cancel and Non-Refundable.